WSHN-XEE2 MF 10.2-120.2
M08R40A15-02
ELECTRICAL CIRCUIT ALARMS
Num
Name
Description
Category
ee2043 Alarm Inverter 3
Inverter 3 in alarm
Inverter APY
ee2044 Alarm missing comunication inv3
Inverter 3 Modbus communication error
Inverter APY
ee2045 Timeout comunication inv3
Inverter 3 communication timeout
Inverter APY
EE2047 Alarm Envelop Comp1
Compressor 1 envelope alarm
Circuit 2
EE2048 Alarm Envelop Comp2
Compressor 2 envelope alarm
Circuit 2
EE2049 Alarm Envelop Comp3
Compressor 3 envelope alarm
Circuit 2
ee2055 Alarm Inverter 1
Inverter 1 in alarm
Inverter DFS
ee2056 Alarm missing comunication inv1
Inverter 1 Modbus communication error
Inverter DFS
ee2057 Timeout comunication inv1
Inverter 1 communication timeout
Inverter DFS
ee2058 Alarm Inverter 2
Inverter 2 in alarm
Inverter DFS
ee2059 Alarm missing comunication inv2
Inverter 2 Modbus communication error
Inverter DFS
ee2060 Timeout comunication inv2
Inverter 2 communication timeout
Inverter DFS
ee2061 Alarm Inverter 3
Inverter 3 in alarm
Inverter DFS
ee2062 Alarm missing comunication inv3
Inverter 3 Modbus communication error
Inverter DFS
ee2063 Timeout comunication inv3
Inverter 3 communication timeout
Inverter DFS
ee2070 User side ECV 1.1
User side ECV connection problem
HW Circuit 2
ee2071 Source ECV 1.1
Source side ECV 1 connection problem
HW Circuit 2
ee2072 Source ECV 2.1
Source side ECV 2 connection problem
HW Circuit 2
R
EFRIGERANT CIRCUIT ALARMS
Num
Name
Description
Category
ff1005
Min overheating EEV1
Value of refrigerant superheat too low EEV1
(user side)
Circuit 1
ff1006
Min overheating EEV2
Value of refrigerant superheat too low EEV1
(source)
Circuit 1
fF1009
Low Pressure Alarm (DI)
Low Pressure Alarm (DI)
Circuit 1
ff1010
Warning LP Cool
Low Pressure Pre Alarm in Cooling Mode
Circuit 1
ff1011
Warning LP Heat
Low Pressure Pre Alarm in Heating Mode
Circuit 1
fF1012
Low pressure Alarm Heat (AI)
Low Pressure in Heating Mode (AI)
Circuit 1
fF1013
High Pressure (DI)
High Pressure Alarm (DI)
Circuit 1
ff1014
Warning High Pressure
High Pressure Pre Alarm
Circuit 1
fF1015
High Pressure Alarm (AI)
High Pressure Alarm (AI)
Circuit 1
ff1016
Max RC Warning
Maximum Pressure Ratio Pre Alarm
Circuit 1
fF1017
Min RC Alarm
Minimum Pressure Ratio Pre Alarm
Circuit 1
fF1018
Low Pressure Alarm Cool(AI)
Low Pressure Alarm in Cooling Mode
Circuit 1
FF1019
Max RC Alarm
Maximum Pressure Ratio
Circuit 1
FF1034
Vacuum Circuit
Vaacum Alarm
Circuit 1
FF1046
LimLp
Low pressure limit
Circuit 1
ff1047
DFRForced
Defrost Forced
Circuit 1
ff1048
DFRWaterTLow
Low water temperature for defrost operation
Circuit 1
ff1049
DFRTimeMax
Defrost Maximum Time
Circuit 1
Summary of Contents for WSHN-XEE2 MF 10.2
Page 13: ...M08R40A15 02 WSHN XEE2 MF 10 2 120 2 13 5 5 Connections performer by customer...
Page 46: ...46 WSHN XEE2 MF 10 2 120 2 M08R40A15 02 9 4 Source side 3 way modulating valve...
Page 47: ...M08R40A15 02 WSHN XEE2 MF 10 2 120 2 47 9 5 Source side 2 way modulating valve...
Page 48: ...48 WSHN XEE2 MF 10 2 120 2 M08R40A15 02 9 6 VALVE FOR DOMESTIC HOT WATER...
Page 63: ...Page intentionally left blank...