ACCESSIBLE PARAMETERS FROM REMOTE OR SERVICE KEYBOARD
num. Par. Description
Value UM
29
Summer secondary Set Point
10
°C
30
Winter secondary Set Point
35 °C
32
Summer Set Point
5.7 °C
33
Winter Set Point
41.2 °C
42
Summer Set Point Maintenance
20 °C
43
Winter Set Point Maintenance
30 °C
44
Enables Summer Maintenance
0 num
45
Enables Winter Maintenance
0 num
77
Antifreeze heater set point
4 °C
80
Antifreeze alarm
4 °C
84
Limit of deactivation before reaching the antifreeze steps
4.5 °C
117
Sanitary water set point
35 °C
163
Configures remote inputs: 1 = H/C by keypad or supervisor
216
Keypad address on Clivet Bus net: 7 =local; 1=remote
0
num
PARAMETER MODIFICATION
1
Push SET button
2
Select the
parameter
3
Modify the value
4
Select another
parameter
5
SET to esc
VISIBLE STATUS FROM REMOTE KEYBOARD OR SERVICE KEYBOARD
UNIT STATA MENU
INDICE DESCRIPTION
VALUE
1
Current Set Point
°C
2
Temperature drop in degrees centigrade given by the compressor including
compensations, if any
°C
3
Resource activation timer
When this value reaches the value fixed at the next status (TimeScan), the thermal
regulator will compare the input temperature with the set point and will activate the
resources (compressor and/or heaters)
Seconds
4
Dynamic TimeScan relating to source activation
Seconds
5
Value in degrees of the external air compensation
°C
6
Value in degrees of the water reset signal compensation
°C
7
summation C CompDuty
°C
8
Value in degrees of the duty-cycle compensation
°C
9
Inlet temperature
°C
10
Outlet temperature
°C
11
Water temperature of refreshing panel
°C
12
Coil temperature (if condensing in water becomes condenser antifreeze probe)
°C
13
Condensing pressure
Bar
14
Fan/Coil percentage 1
0-100%
15
Heater output temperature
°C
16
WBAN condensing pressure
Bar
18
Water Reset signal value
4-20 mA