CLIVET WSHN-EE 101 Installation And Use Manual Download Page 25

 

  

pag 

25 

SANITARY HOT WATER: COMPENSATION OF THE SET POINT FOR EXTERNAL TEMPERATURE 

The set point can be compensated according to the external temperature in 2 modes:  

1.  hot season thermal efficiency curve  

when the external temperature is high, the sanitary hot water set point is decreased; in this manner the thermal 
efficiency is increased  
curve A in the graph  
the compensation is enabled in the standard configuration  

2.  compressor operation limit 

when the external temperature is particularly cold, the sanitary hot water set point is decreased in order to guarantee 
operation of the compressor even near its operation limits  
curve B in the graph 
the compensation must be enabled during start-up 
 

PARAMETERS INDICATIVE 

VALUES 

par Description 

Meaning 

value 

12 

CextMaxH 

Ext. Temp. max. winter correction 

15 

13 

CextMinH 

Ext. Temp. min. winter correction 

73 EnLimiteTExtH 

Enable corr. SP Heat for external air limit 

74 TlimiteMaxH 

Outside temperature for max SP Heat 

-5 

115 CompExtH2OS 

Enable comp. for External Temp. of the sanitary hot water set point 

116 MaxCompH2OS 

Maximum outside T correction for sanitary hot water set point 

10 

152 

TextEn 

EXT. Air probe presence 1=YES, 0=NO 

 

160 TlimiteMinH 

Outside temperature for min SP Heat 

-15 

175 MinSetLimiteH 

Minimum value that can be set for SP Heat 

35 

 

 

T EXT 

P 12

P 13

SET POINT

40 °C

37 °C

P 175

P 74 

P 160

A

B

T EXT 

15°C

7 °C

SET POINT

40 °C

37 °C

35 °C

-2 °C

-15 °C

A

B

Summary of Contents for WSHN-EE 101

Page 1: ...TER M03S40F6 HN R TO WA 6 11 EE 71 ATER HE CIRCUI Instal 17 81 AT PUM IT FOR IN llation 7 21 91 P REVER NDOOR n and U 31 101 RSIBLE O INSTALL Use M 41 5 12 ON THE LATION anual 51 6 1 REFRIG 61 GERANT...

Page 2: ......

Page 3: ...NNECTION TO THE MAINS 20 SYSTEM COMPOSITION 20 FUNCTIONAL CONNECTIONS 21 S T A R T U P 2 9 PRELIMINARY CHECKS 29 REFRIGERANT SYSTEM 29 WATER SYSTEM 29 ELECTRICAL SYSTEM 29 VERIFy tensions absorptions...

Page 4: ...UMBER This provides unique identification of the machine It makes it possible to trace the specific features of the unit and to identify the components installed in it Without this number it is not po...

Page 5: ...robes from a depth of 30 to 100 m 6 groundwater collector disposal wells 7 When it cools the refrigerant becomes liquid 8 The expansion valve causes a sudden drop in the pressure of the refrigerant wh...

Page 6: ...r either towards the sanitary hot water storage or towards the heating equipment 3 sanitary hot water storage 4 fan coil heating 5 if the room needs to be heated the 3 way valve diverts the water towa...

Page 7: ...ining the system at a safety temperature in WINTER MAINTENANCE function Put the unit in OFF parameter 45 must be 1 yellow led is flashing Minimize the consumptions maintaining the system at a safety t...

Page 8: ...Control parameter 29 Modify the water temp in MAINTENANCE heating Control parameter parametro 43 Modify the water temp in MAINTENANCE cooling Control parameter 42 COMMON CAUSES OF SHUTDOWN 1 set poin...

Page 9: ...r and glycol mix for air conditioning within the limits defined in the technical bulletin and this manual Any use other than that specified does not imply any commitment or constraint by the manufactu...

Page 10: ...RISKS A smell of burning smoke or other indications of serious irregularity could signal the onset of situations liable to cause damage to persons or property or to the unit itself Isolate the unit fr...

Page 11: ...FRIG 8 Product R 410A Identification of the supplier See heading or bottom of page No of emergency telephone See heading or bottom of page 02 Composition information on ingredients Substance Compound...

Page 12: ...e driver compartment Verify that the driver is informed on the potential risk of the load and that he knows what to do in case of an accident or emergency Before starting the transport verify that the...

Page 13: ...the circuits can assume values which activate the safety valves HANDLING The operation of handling the unit must be carried out respecting the instructions of the safety norms in force Legislative Dec...

Page 14: ...e only to qualified and authorized personnel 2 SAFETY VALVE only if present on the unit the installer is responsible for evaluating the opportunity of installing drain tubes in conformity with the loc...

Page 15: ...ubes with heating cables under the tubes insulation empty the system by verifying that o no taps are closed so they can not trap the water even after emptying o there are no low points where the water...

Page 16: ...in the event of the following the water in the system is very low the unit will not be used in a private house in an industrial process or other USE SCHEMA 1 Heating integration 2 3 ways ON OFF sanit...

Page 17: ...FLOW RATE This makes it possible to limit water consumption increase energy efficiency and extend the unit s operating limits It can be modified by using 1 Modulating motorized valve 2 Cut off valve 3...

Page 18: ...the ELECTRICAL CONNECTIONS section double temperature underfloor heating manages the elements of a mixed system with underfloor piping fan coil radiators circulator mixer valve outlet probe see detai...

Page 19: ...should be determined according to the plant features The section of supply cables and protection cable must be seized according to the characteristics of the protections used SIGNALS DATA LINES Do no...

Page 20: ...heck the shipping document descriptions USER AMBIENT TERMINAL Permits setting the unit function modes cooling heating ECO and to display the alarms ELECTRIC REFRIGERATOR WATER This is standard on cert...

Page 21: ...SET POINT COMPENSATION with 4 20 mA signal 12 interface via RS485 1 ON OFF FROM REMOTE CONTROL Generally the unit is delivered with bridged terminals if the control is not used the bridge should not...

Page 22: ...ower than par 180 1 1 MAIN ADJUSTMENT UNIT IN HEATING MODE in heat pump mode the compressor is disabled 2 1 POWER LIMITATION ACCORDING TO EXTERNAL TEMPERATURE the following behaviour occurs as the ext...

Page 23: ...in case of unit shutdown MAINTENANCE With the unit coupled to a boiler the maintenance function if enabled activates the boiler instead of the heat pump if necessary The diagram on the side is indicat...

Page 24: ...COND SET POINT it is necessary to set par 50 2 In this mode the inputs on the main card will be configured as follows CN1_10 11 sanitary hot water request CN1_14 16 second set point Refer to the wirin...

Page 25: ...ear its operation limits curve B in the graph the compensation must be enabled during start up PARAMETERS INDICATIVE VALUES par Description Meaning value 12 CextMaxH Ext Temp max winter correction 15...

Page 26: ...anels can be managed in three ways 1 the valve is managed to maintain the outlet temperature at par 192 value independently of the unit operating mode COOLING or HEATING 2 calculated automatically in...

Page 27: ...HEATING 11 SET POINT COMPENSATION ON THE TEMPERATURE OR EXTERNAL ENTHALPY Optimises unit energy efficiency by automatically adjusting the set point according to enthalpy or the external temperature R...

Page 28: ...s twisted and shielded Section of conductor 0 22mm2 0 35mm 2 Nominal capacity between conductors 50 pF m nominal impedance 120 Recommended cable BELDEN 3105 A TYPE OF NETWORK The serial lines must be...

Page 29: ...eck that there is no air in the circuit If required bleed it using the vent valves in the system When using antifreeze solutions make sure the glycol percentage is suitable for the type of use envisag...

Page 30: ...te L h The cooling power is shown in the TABLE ON GENERAL TECHNICAL DATA included in this manual referred to specific air water conditions or in the tables on cooling PERFORMANCE IN THE TECHNICAL BULL...

Page 31: ...ION The thermoregulation is based on the OUTLET temperature The unit is dimensioned for a determined TOTAL HEAD between input and output water temperature Usually the project step is 5 C if the value...

Page 32: ...tatus 1 static set point The static set point can so be modified in a dynamic way by two CORRECTIONS based on as many unit external factors correction based on the ext temp enthalpy correction based o...

Page 33: ...rculation pump measures the water temperature and activates the compressor if required to take the water temperature to the set point level Summer maintenance set point par 42 Winter maintenance set p...

Page 34: ...erating mode leds remain alight even when the machine is in the maintenance status The maintenance set points if activated control the water temperature when the unit is OFF or on STANDBY To do this t...

Page 35: ...faulty Allarme serial faulty Allarme serial faulty FUNCTIONING TEST The Test key allows the verification of the proper functioning of the all six signalisation LEDs When it is pressed all leds are ON...

Page 36: ...Point C 2 Temperature drop in degrees centigrade given by the compressor including compensations if any C 3 Resource activation timer When this value reaches the value fixed at the next status TimeSc...

Page 37: ...e repeated resetting could cause irreversible damage To avoid this the unit can only be reset MANUALLY from the keyboard only when the cause for the alarm has been removed PRE ALARMS and SIGNALS warn...

Page 38: ...w Auto E 18 System charged with water MANUAL E 19 Phase monitor Auto E 20 Antifreeze alarm MANUAL C 21 Antifreeze PREAlarm Auto C 22 High pressure PreAlarm Auto C 24 Pump change Auto E 25 flow alarm C...

Page 39: ...re this problem may occur Check that the panelling is fastened correctly Poor fastening may give rise to malfunctions and abnormal noise and vibration MAINTENANCE INSPECTIONS Foresee inspection assist...

Page 40: ...or cooling units or when seasonal switching should be performed When restarting refer to the SWITCHING ON section Schedule technical assistance in advance to avoid hitches and be able to use the insta...

Page 41: ...0 8 69 16 0 44 28 60 46 43 78 38 84 26 01 5 2 6 92 22 65 8 79 2 73 7 73 16 2 44 77 60 95 44 24 39 32 26 46 5 4 7 96 23 70 9 77 3 73 6 79 16 4 45 26 61 44 44 69 39 79 26 90 5 6 8 97 24 73 10 72 4 71 5...

Page 42: ...85 45 47 37 6 82 67 98 58 78 62 76 01 60 26 26 8 66 37 82 56 64 07 60 18 45 77 37 8 82 94 98 84 78 86 76 27 60 50 27 0 66 71 82 90 64 38 60 51 46 08 38 0 83 20 99 09 79 09 76 53 60 73 27 2 67 05 83 2...

Page 43: ...ded or included other uses are isolated etc 4 Dirt water filter valves open air bubbles in the plant 5 dirty exchanger 6 Manostat transducer loose electric contacts terminals wiring cables interrupted...

Page 44: ...irt pin blocked mechanically LOW PRESSURE heating 1 low water temperature see operating limits 2 insufficient water flow to the exchanger high thermal difference between input and output 3 not CONSTAN...

Page 45: ...ored in special containers When recovering the substances present in the unit all measures must be taken to avoid damaging persons and things and polluting the surrounding area Awaiting dismantling an...

Page 46: ...9 5 44 4 155 134 Water content l 0 6 0 6 0 8 0 8 0 9 1 1 2 2 2 5 2 9 2 9 3 2 EXSTERNAL EXCHANGER Type of internal exchanger 4 PHE No of internal exchangers 1 Water flow rate Internal Exchanger 1 l s 0...

Page 47: ...al exchangers 1 Water flow rate l s 0 45 0 49 0 59 0 77 0 99 1 23 1 48 1 66 1 89 2 12 2 39 max Water flow rate l s 0 76 0 82 0 99 1 28 1 65 2 05 2 47 2 77 3 15 3 53 3 99 Pressure drop kPa 28 31 31 43...

Page 48: ...certification The sound pressure is measured at 1 m from the external surface of the unit in open field conditions data referred to the following conditions internal exchanger water 12 7 C external ex...

Page 49: ...OPTIONAL 14 3 WAYS VALVE OPTIONAL 15 CLEARANCE ACCESS RECOMMENDED 16 POWER INPUT 17 1 2 GAS CHARGE FITTING G BARYCENTRE M mm 193 190 195 193 176 N mm 173 173 173 170 187 O mm 169 170 172 168 171 P mm...

Page 50: ...NDED 16 POWER INPUT 17 19 1 2 GAS CHARGE FITTING SIZES 61 71 81 91 18 19 1 2 GAS CHARGE FITTING SIZES 101 121 G BARYCENTRE M mm 154 167 178 185 187 189 N mm 213 200 191 182 180 178 O mm 286 300 330 33...

Page 51: ......

Page 52: ...info clivet es CLIVET UK LTD Fareham Hampshire U K Tel 44 0 1489 572238 Fax 44 0 1489 573033 info clivet uk co uk CLIVET NEDERLAND B V Amersfoort Netherlands Tel 31 0 33 7503420 Fax 31 0 33 7503424 in...

Reviews: