Remote control of the unit
(without PEND00017 Remote interface module for REMAUX
auxiliary controls)
With S5_3 ON, the unit is controlled remotely.
Wired controller disabled.
ON/OFF state:
controlled by the On/Off input
input ON = unit ON
With the units in modular configuration, remote control must be
applied to the master unit, which transmits it to the slave units.
After having set S5_3 disconnect and reconnect the power supply
to confirm the change.
Remote control of the unit
(with PEND00017 Remote interface module for REMAUX auxiliary
controls)
With S5_3 in OFF, for operation see the instructions of the
accessory supplied separately.
Unit in modular configuration
Set the correct date and time on each unit before connecting
them to the network
Enable multiple configuration:
SW12-2 :
ON units in multiple configuration
OFF single unit
The modular configuration consists of two networks: the
controller network and the unit network (main boards).
Each network can have up to 16 addresses (from 0 to 15) and
must be addressed separately.
Each network has its own master, which must have address = 0.
Modular configuration - Addressing units
They are addressed through the encoder ENC4 on the back of
the keypad.
The address corresponds to the encoder no.
The address is shown on the display DSP1.
Es: MASTER : address = 0 encoder = 0
SLAVE 1 : address = 1 encoder = 1
SLAVE 15 : address = 15 encoder = F
Modular configuration - Addressing controls
A maximum of 16 controls can be addressed, with address from
0 to 15; so for example:
16 units with relative controller on board, one of which is the
master
15 units with relative controller on board + a remote controller
as the master
Press MENU +
►
for 3 seconds
Press ▲▼
to select the address