![CLIVET WSAT-YES 18.2 Manual Download Page 10](http://html1.mh-extra.com/html/clivet/wsat-yes-18-2/wsat-yes-18-2_manual_2625599010.webp)
Avoid therefore:
obstacles to the airflow
exchange difficulties
leaves or other foreign bodies that can obstruct the exchange
batteries
winds that hinder or favour the airflow
heat or pollution sources close to the unit (chimneys,
extractors etc)
stratification (cold air that stagnates at the bottom)
recirculation (expelled air that is sucked in again)
positioning below the level of the threshold, close to very high
walls, attics or in angles that could give rise to stratification
or recirculation phenomenons.
Ignoring the previous indications could:
energy efficiency decrease
alarm lockout due to HIGH PRESSURE (in summer) or LOW
PRESSURE (in winter)
Pressure relief valve gas side
The installer is responsible for evaluating the opportunity of
installing drain pipes in compliance with the local regulations in
force (EN 378).
If ducted, the valves must be sized according to EN13136
.
Functional spaces Safety Zone
Do not smoke or use open flames within this area
A
B
C
D
E
G
F
G
G
F
A = 800 mm
B = 500 mm
C = 800 mm
D = 500 mm
E = 6000
F = 500 mm
G = 500 mm
mm