8.6 Electric
fans
Check:
•
the fans and the relative protection gridsare well fixed
•
the fan bearings (evident by noise and anomalous vibrations)
•
the terminal protection covers are closed and the cable holders are properly positioned
8.7 Water side exchanger
It is very important for the exchanger to be able to provide the maximum thermal exchange, therefore it is essential for the inner surfaces to
be clean of dirt and incrustations.
Periodically check the difference between the temperature of the supply water and the condensation temperature: if the difference is greater
than 8°C–10°C it is advisable to clean the exchanger.
The clearing must be effected:
•
with circulation opposite to the usual one
•
with a speed at least 1,5 times higher than the nominal one
•
with an appropriate product moderately acid (95% water + 5% phosphoric acid)
•
after the cleaning rinse with water to inhibit the action of any residual product
8.8 Circulating
pumps
Check:
•
no leaks
•
bearing status (anomalies are highlighted by abnormal noise and vibration)
•
the terminal protection covers are closed and the cable holders are properly positioned
8.9 Water
filter
Check that no impurities prevent the correct passage of water.
8.10 Flow Switch
•
controls the operations
•
remove incrustations from the palette
8.11 Compressor supply line shut-off valve
Do not remove the seal
Remove only if authorized by the manufacturer.
Please contact the maker for informations.
8.12 Crankcase heater
Check:
•
closure
•
Operation