22 WSAT-XEM
50.4-120.4
M0L240E16-01
6.11 Climatic TExt
Menu accessible only after having entered the password.
Access reserved only to specifically trained personnel.
The parameter modification can cause irreversible damages.
The setpoint defined by the temperature curve is shown at status S0052: ActualUtSetp
Only if P0036: EnCompExt ≠ 0
Path: Main Menu / Unit parameters / TExt Correction config
Example
Step
Display
Action
Menu/Variable
Keys
Notes
1
Press 3 sec.
2
Password
Set
Password
3
Press
4
Main menu
Select
Unit parameters
5
Unit parameters
Select
Climatic TExt
6
Climatic TExt (pwd)
Select
Parameter
7
Set
8
Confirm
9
Press 3 sec.
10
Select
Local connections
Path: Main Menu / Unit parameters / TExt Correction config
Parameters
Short description
Description
P0606
CSptLow
setpoint temperature value when the air temperature value is AirAtSptLowC
P0607
AirAtSetPointLowC
external air temperature value where the calculated setpoint takes on the value given by CSptLow
P0608
CSptHigh
setpoint temperature value when the air temperature value is AirAtSptHigC
P0609
AirAtSetPointHighC
external air temperature value where the calculated setpoint takes on the value given by CSptHigh
P0610
HSptLow
setpoint temperature value when the air temperature value is AirAtSptLowH
P0611
AirAtSptLowH
external air temperature value where the calculated setpoint takes on the value given by HSptLow
P0612
HSptHigh
setpoint temperature value when the air temperature value is AirAtSptHigH
P0613
AirAtSptHigH
external air temperature value where the calculated setpoint takes on the value given by HSptHigh
P0606 / P0609: Coooling
P0610 / P0613: Heating