24 WSAT-XEM
50.4-120.4
M0L240E16-01
6.13 ECOSHARE function for the automatic management of a group of units
•
Max 7 units
•
Maximum length of the bus line: 700 m.
•
Maximum distance between 2 units: 300 m
•
Type of cable: shielded twisted pair cable Ø 0,8 mm. use an EIB/KNX cable
•
Possible connections: Tree, star, in/out bus, mixed
•
It is not possible to use a ring connection
•
No end-of-line resistor or terminator required
•
There must be suitable arresters to protect the serial lines from the effects of atmospheric discharges
•
The data line must be kept separate from the power conductors or powered at different voltage values and away from possible sources
of electrical interference