14
WSAN-YES 18.2-35.2
M0ST10N19-00
TW Probe - Total water
It must be installed on the supply of the unit, as far away
as possible.
SINGLE UNIT: antifreeze function
MODULAR UNIT: thermoregulation (see diagram below)
4 WATER CONNECTION
Taf1
T5
Tw
Unit in modular configuration
Maximum 16 total units.
Maximum 4 units in the same water branch.
The modular system is controlled by the MASTER unit (address=0),
→
Electrical connections
All units must be electrically connected to each other con cavo schermato a 3 conduttori
→
Electrical
connections
Each module must be configured with the water fittings for modular unit (AMOD).
Each module can be equipped with inertial system storage tank (ACIMP).
It is not possible to have a hydronic assembly installed on board.
It is necessary to provide an external pumping unit, sized for the entire capacity of the modular system
( r esponsibility of the Customer ) . The pumping unit will be managed by the Master unit through a potential-free
contact and 0-10V signal →
electrical connections
DHW managament in modular configuration
Each unit with ACS option must have its own DHW storage
Each unit with DHW option must have its own DHW storage tank.
The pumping unit is managed directly by the unit with ACS option via clean contact (PUMP-N)
The management of domestic hot water takes priority over the system
→
Domestic hot water