14.4 Boiler management
Indicative diagram - see wiring diagram
A
Domestic hot water module
L.300 x P.220 x H.120
B
Temperature probe domestic hot water
cable length 5 mt
C
Boiler
provided by the Customer
D
3-way DHW valve
accessory YVACS
E
3-way valve
accessory YVACS
F
1° setpoint control
On-off (on = 1°setpoint, off = boiler off)
G
2° setpoint control (2 setpoint>1 setpoint)
On-off (on = 2° setpoint)
H
max 100 mt
Min. 0,35 Max.1 mm2
I
Control F delay respect to control E
Enable boiler:
•
par br00 = 3
Setpoint (C) < heat pump operation range
ON control F = ON control E+ 30 sec.
A
Boiler in integration to the heat pump
B
Boiler replacing the heat pump
Based on the system water temperature / domestic hot water
Br02 = 0 (Factory value)
Based on the outdoor air temperature
Enable the function:
HP00=1
Main menu
→
Parameters
→
br
Main menu
→
Parameters
→
HP