M0R940E13-00
WSAN-XIN 21-141
31
In the following example the scheduling 1 schedules:
at 07:00 changes the cooling set-point
at 12:00 changes the cooling set-point
at 16:30 changes the cooling set-point
at 22:00 changes the cooling set-point
Scheduling 1
Description
Event 1
Event 2
Event 3
Event 4
Time
tE10 = 07
tE17 = 12
tE24 = 16
tE31 = 22
Minutes
tE11 = 00
tE18 = 00
tE25 = 30
tE32 = 00
Mode 0= on
1= standby
tE12 = 0
tE19 = 0
tE26 = 0
tE33 = 0
*Cooling tempera-
ture
tE13 = -
tE20 = -
tE27 = -
tE34 = -
*Heating tempera-
ture
tE14 = 20
tE21 = 22
tE28 = 22
tE35 = 18
DHW temperature
tE22 = 45
tE22 = 45
tE29 = 55
tE36 = 45
* If the unit is in Cooling is used the cooling temperature.
* If the unit is in Heating is used the heating temperature.
Event 1
Sched. 1 (par.)
Sched. 2 (par.)
Sched. 3 (par.)
Time
tE10
tE38
tE66
Minutes
tE11
tE39
tE67
Mode 0= on
1= standby
tE12
tE40
tE68
Cooling tem-
perature
tE13
tE41
tE69
Heating tem-
perature
tE14
tE42
tE70
DHW tempera-
ture
tE15
tE43
tE71
Event 2
Time
tE17
tE45
tE73
Minutes
tE18
tE50
tE74
Mode 0= on
1= standby
tE19
tE47
tE75
Cooling tem-
perature
tE20
tE48
tE76
Heating tem-
perature
tE21
tE49
tE77
DHW tempera-
ture
tE22
tE50
tE78
Event 3
Time
tE24
tE52
tE80
Minutes
tE25
tE53
tE81
Mode 0= on
1= standby
tE26
tE54
tE82
Cooling tem-
perature
tE27
tE55
tE83
Heating tem-
perature
tE28
tE56
tE84
DHW tempera-
ture
tE29
tE57
tE85
Event 4
Time
tE31
tE59
tE87
Minutes
tE32
tE60
tE88
Mode 0= on
1= standby
tE33
tE61
tE89
Cooling tem-
perature
tE34
tE62
tE90
Heating tem-
perature
tE35
tE63
tE91
DHW tempera-
ture
tE36
tE64
tE92
Summary of Contents for WSAN-XIN 21-141
Page 4: ...4 WSAN XIN 21 141 M0R940E13 00...
Page 44: ...44 WSAN XIN 21 141 M0R940E13 00 9 13 Spare parts sizes 21 31 41...
Page 46: ...46 WSAN XIN 21 141 M0R940E13 00 9 14 Spare parts sizes 51 71...
Page 48: ...48 WSAN XIN 21 141 M0R940E13 00 9 15 Spare parts sizes 81 101...
Page 50: ...50 WSAN XIN 21 141 M0R940E13 00 9 16 Spare parts sizes 121 141...
Page 70: ...70 WSAN XIN 21 141 M0R940E13 00...