Voltage
Check that the air and water temperatures are within in the
operating limits.
Start-up the unit.
While the unit is operative, i.e. in stable conditions nearing
operating ones, check:
Power supply voltage
Total absorption of the unit
Absorption of the single electric loads
Options
Menu accessible only after having entered the password. Access
reserved only to specifically trained personnel.
The parameter modification can cause irreversible damages.
Path: Main menu / Unit parameters / Options
Parameters
Short description Description
P0050
En Demand limit Enabling Demand Limit: 0 = disabled, 1 = analogic input, 2 = parameter
P0051
En Water reset Enabling Water reset: 0 = Off, 1 = Cool, 2 = Heat, 3 = Cool and Heat
P0052
En 2SetPoint
Enabling 2SetPoint: 0 = Off, 1 = On
P0053
En Climatica
Enabling Climatic 0 = Off, 1 = Cool, 2 = Heat, 3 = Cool and Heat
P0054
PrioritaCmd
Status and machine mode priority: Local [0] = Priority to local commands, BMS [1]
priority to commands from plant supervisor
P0055
En DI On-Off
Enabling remote ON-OFF: 0 = Off, 1 = On
P0061
Enable scheduler Enable scheduler : 0 = Off, 1 = On
P0062
TypeDL
Inlet signal type: 0 = 0-10V; 1 = 4-20mA
P0063
TypeWR
Inlet signal type: 0 = 0-10V; 1 = 4-20mA