Concentration
[-] o [mg/l]
Copper
pH-Value
<6
6-8
>8
0
+
+
Chloride (CI-)
<10
10-100
100-1000
>1000
+
+
+
0
Sulphate
<50
50-200
>200
+
0
-
Nitrates
<100
+
Free & aggressive Carbonic Acid
<5
5-20
>20
+
0
-
Oxygen
<1
1-8
>8
+
+
0
Ammonium
<2
2-20
>20
+
0
-
Ferric und Manganese
>1
0
Sulfides
-
Free Chlorine
<5
+
Deposable substances
0
Recommendations on using copper pipes with substances contained in the
water
Water filter
Must be installed immediately in the water input of the unit,
in a position that is easily accessible for cleaning.
The filter never should be removed, this operation invalidates
the guaranty.
The filter must have an adequate mesh to prevent the entry of
particles greater than:
0,87 mm