M03I40M7-03 15/11/07
page
29
ACCESSIBLE PARAMETERS
PARAMETER MENU STRUCTURE
PARAMETERS
Set
LIST
Thermoreg.
Antifreeze
LIST
Maintenance
LIST
Set - point
LIST
SCHEDULING
Enscheduling
LIST
Configure
LIST
CLOCK SETUP
Clock
LIST
Data
LIST
menu: PARAMETERS – THERMOREG. – SET POINT
DEFAULT values
90 / CEN
SecondSetC
Secondary cooling Set Point
12
91 / CEN
SecondSetH
NOT USED - Secondary heating Set Point
35
118 / CEN
SetCool
Cooling Set Point
6.5
119 / CEN
SetHeat
NOT USED - Heating Set Point
45
272 / CEN
SetRecovery
NOT USED
35
menu: PARAMETERS – THERMOREG. – MAINTENANCE
114 / CEN
SetMantCool
Summer maintenance setpoint
15
117 / CEN
SetMantHeat
NOT USED - Winter maintenance setpoint
30
menu: PARAMETERS - THERMOREG.– ANTIFREEZE
115 / CEN
AllFreeze
Antifreeze alarm set
4
121 / CEN
PreAF
Antifreeze pre-alarm set
4.5
261 / CEN
SetResist
Antifreeze heater set
4
menu: PARAMETERS – SET – UNIT - EVAPORATORS
37 / EVAP
SetResist
Antifreeze heater set
4
39 / EVAP
ALLFreeze
Antifreeze alarm set
4
41 / EVAP
PreAF
Antifreeze pre-alarm set
4.5