POSITIONING
GENERAL
For installing air-conditioning systems, it is necessary to
consider the following:
•
the technical spaces necessary for the machine and
system
•
the place where the machine will be installed
•
the transport of thermal carrier fluids and relevant
connections to the unit:
o
water
o
air
o
refrigerant (unit in more sections)
•
electrical connections
If these aspects are not evaluated carefully, they can affect
the performances and the working life of the unit.
FUNCTIONAL CLEARANCES
When placing the unit, please respect the functional
clearances indicated in DIMENSIONS section.
The functional spaces need to be observed because of the
following:
•
to guarantee the good operation of the unit
•
to allow the performance of all maintenance operations
•
to protect the authorized operators and exposed people
If more units are placed close to one another, the functional
spaces must be doubled.
POSITIONING
1. The units are designed for
INDOOR
installations,
performed in fixed positions and in areas accessible
only to qualified and authorized personnel
2.
SAFETY VALVE
(only if present on the unit) : the
installer is responsible for evaluating the opportunity of
installing drain tubes, in conformity with the local
regulations in force ( EN 378 )
3.
Install the unit
raised
from the ground
4.
avoid installations in places subject to
flooding
5. Verify that the fixing/supporting points are level and
suitable to support the
weight of the unit
(see the
weight and the weights distribution)
6. It is recommended to put the unit on specific
antivibration devices
Each support point of the unit sustains a different
weight. Therefore, each anti-vibration device is sized for
a specific support point, and can only be placed there.
The anti-vibration devices must therefore be placed in
accordance with the instructions provided with them
and with the dimensional drawings in which the support
points are indicated by W1 , W2 , W3 etc .
On each anti-vibration device (if provided by CLIVET),
its identifying code is stamped, for example C6100100
Flexible joints
are necessary on all the hydraulic/
aeraulic connections (the joints are not supplied by
Clivet)
INSTALLING ANTIVIBRATION MOUNTS
C6100026-28
C6100030-32