2.2 Constraint Cooling
1.Constraint Cooling
Fig.2-1
SW2 Check Query button
SW1 Constraint cooling button
MAIN BOARD
(OUTDOOR UNIT)
62
33.5kW
40kW
45kW
48
Mode
Force cooling rate(Hz)
Outdoor unit main control board has constraint cooling key: SW1
(see
Fig.2-1
). One press will send constraint cooling signal to all
the indoor unit. Constrain all the indoor unit to constraint cooling
operation. Outdoor units operate as the fixed frequency shown in
Table 2-2. Indoor unit fan operate at a high speed and press the
key again to log out constraint cooling mode.
Table 2-2
2. Spot check
Check in the outdoor main control panel is the spot check button
(refer to Fig.2-1), and press this button, the digital pipe of the
main control panel will circulating display the parameters (display
one parameter every press this button) as the following table 2-3
sequence.
Table of force cooling frequency
Table 2-3
0
8
ˈ
10
ˈ
12
ˈ
14
ˈ
16
ˈ
18
0
ˈ
2
ˈ
3
ˈ
4
0
ˈ
1
ˈ
……
ˈ
9
ˈ
10
0
ˈ
1
ˈ
2
ˈ
3
ˈ
4
0
ˈ
1
ˈ
2
ˈ
3
ăă
SW2 Query instructions
12
Normal display
Display content
Outdoor unit address
Outdoor unit itself capacity
Moduler outdoor unit Qty
Qty.setting of indoor units
Total capacity of outdoor unit
Total requirement of indoor unit capacity
Total requirement of main unit corrected capacity
Operation mode
This outdoor unit actual operation capacity
Speed of fan A
Speed of fan B
T2B/T2 average Temp.
T3/T3A pipe Temp.
T4 ambient Temp
Discharge Temp.of Inverter compressor A
Current of inverter compressor A
Opening angle of EXV A
Opening angle of EXV B
High pressure
T3B
Qty. of Indoor units
Qty. of the working Indoor units
Priority mode
Night noise control mode
Static pressure mode
DC voltage A
DC voltage B
Note
Available for main unit
Reserve
Actual value
Actual value
Actual value
Actual value
Actual value
Capacity requirement
Actual value
Actual value
Reserve
Reserve for 33.5kW/40kW
That can communicate with indoor units
Actual value
Reserved
Actual value÷10
Without error or protection,display code 8.8.
Check end
Discharge Temp.of Inverter compressor B
Radiator temperature
Current of inverter compressor B
Version of the program
The last error or protection code
0
ˈ
1
ˈ
……
ˈ
9
ˈ
10
Actual value÷10
Reserve
Available for main unit
Available for main unit
06$1;0L77
2ZQHUVPDQXDO
Summary of Contents for MSAN-XMi 120T
Page 1: ...M 1 01 20 03 2019 SAN X J Installation and oXOFShT manual JS DPPMFE heat pump outdoor VOJU 5 5...
Page 4: ...3DJH LQWHQWLRQDOO OHIW EODQN 06 1 0L 0 7...
Page 5: ...Installation manual 8 06 1 0L 0 7 QVWDOODWLRQ PDQXDO...
Page 6: ...3DJH LQWHQWLRQDOO OHIW EODQN 06 1 0L 0 7 QVWDOODWLRQ PDQXDO...
Page 19: ...0wner s manual 6 8 06 1 0L 0 7 2ZQHU V PDQXDO...
Page 29: ...FSUJGJDBUJPOT 06 1 0L 0 7 2ZQHU V PDQXDO...
Page 30: ...Page intentionally left blank 06 1 0L 0 7 2ZQHU V PDQXDO...
Page 33: ...SAN X J 5 5 Installation and oXOFShT manual JS DPPMFE IFBU QVNQ PVUEPPS VOJU...
Page 36: ...1BHF JOUFOUJPOBMMZ MFGU CMBOL 0 0 1 06 1 0L 7 7...
Page 37: ...Installation manual 8 0 0 1 06 1 0L 7 7...
Page 38: ...1BHF JOUFOUJPOBMMZ MFGU CMBOL 0 0 1 06 1 0L 7 7...
Page 51: ...0wner s manual 6 8 0 0 1 06 1 0L 7 7...
Page 52: ...0 0 1 06 1 0L 7 7...
Page 61: ...M 01 16 07 18 SAN X J 5 5 Installation and oXOFShT manual JS DPPMFE heat pump outdoor VOJU...
Page 64: ...1BHF JOUFOUJPOBMMZ MFGU CMBOL 06 1 0L 7 7...
Page 65: ...Installation manual 8 06 1 0L 7 7...
Page 66: ...1BHF JOUFOUJPOBMMZ MFGU CMBOL 06 1 0L 7 7...
Page 83: ...0wner s manual 6 8 06 1 0L 7 7...
Page 84: ...06 1 0L 7 7 1BHF JOUFOUJPOBMMZ MFGU CMBOL...
Page 91: ...1BHF JOUFOUJPOBMMZ MFGU CMBOL...