CLIVET MSAN-XMi 120T Installation And Owner'S Manual Download Page 16

Please select power source for indoor unit and outdoor 
unit respectively 

The power supply has specified branch circuit with leakage 
protector and manual switch.  

The outdoor unit model which corresponding to different outdoor
 unit power supply should refer to the nameplate.(Please set all the 

Please put the connective wire system between indoor unit
and outdoor unit with the refrigerant system together.

Use 3-core shielded wire as indoor unit and outdoor unit signal 
wire. 

The installation should comply with local electric standard. 

Power wiring should be engaged by specialized electrician.

CAUTION

5.1   Outdoor Unit Wiring

The Specification of Power

Table 5-1

Equipment complying with IEC 61000-3-12.
A disconnection device having an air gap contact separation 
in all active conductors should be incorporated in the fixed 
wiring according to the National Wiring Regulation.

CAUTION

The reserved  function is indicated in broken line table,users 
can select  it  when necessary.

CAUTION

Indoor/Outdoor Unit Signal Wire

Connect the wire according to their numbers.

For 10.5~18kw

Fig. 5-4

Outdoor 
Unit

Indoor 
Unit

Power (220-240V~ 50Hz 1-Phase

           (220-240V~ 60Hz 1-Phase)
           (208-230V~ 60Hz 1-Phase)

Power wiring 
(indoor)

Communication Bus

Indoor 
Unit

Indoor 
Unit

wire distribution box

Switch / Circuit breaker

Switch / Circuit breaker

Power wiring 
(outdoor)

Central control
monitor (CCM) 

CCM

Computer

 in broken line table, users can purchase the Central 
control montior when necessary.please contract
with local supplier in details .

Power (380-415V~ 50Hz 3-Phase)
           (380-415V~ 60Hz 3-Phase)
           (208-230V~ 60Hz 3-Phase)

indoor unit power of one system into the same branch circuit.)

14

50

220-240

198

264

36.25

30

40

/

13.5

2×0.1

2×0.9

10.5

50

220-240

198

264

27.5

24

32

/

9.7

0.17

1.7

8

50

220-240

198

264

26.25

24

25

/

9.7

0.17

1.7

16

50

220-240

198

264

36.25

30

40

/

16.1

2×0.1

2×0.9

12

60

208-230

187

253

31.25

30

40

/

13.5

2×0.1

2×0.9

14

60

208-230

187

253

36.25

30

40

/

13.5

2×0.1

2×0.9

16

60

208-230

187

253

36.25

30

40

/

16.1

2×0.1

2×0.9

14

50

380-415

342

456

16.25

15

25

/

9.3

2×0.1

2×0.9

16

50

380-415

342

456

17.5

15

25

/

12

2×0.1

2×0.9

14

60

380-415

342

456

16.25

15

25

/

9.3

2x0.1

2x0.9

16

60

380-415

342

456

17.5

15

25

/

12

2x0.1

2x0.9

10.5

60

208-230

187

253

27.5

24

32

/

9.7

0.17

1.7

12

50

220-240

198

264

31.25

30

32

/

13.5

2×0.1

2×0.9

Model

Capicity(kW)

Hz

Voltage

Min.(V)

Max.(V)

MCA

TOCA

MFA

MSC

RLA

kW

FLA

220-240V~ 1Ph 50Hz

208-230V~ 1Ph 60Hz

12

50

380-415

342

456

15

15

25

/

9.3

2×0.1

2×0.9

380-415V 3Ph~ 50Hz

12

60

380-415

342

456

15

15

25

/

9.3

2x0.1

2x0.9

380-415V 3Ph~ 60Hz

Power 
Supply

Compressor

OFM

Power Source

06$1;0L07

,QVWDOODWLRQPDQXDO

Summary of Contents for MSAN-XMi 120T

Page 1: ...M 1 01 20 03 2019 SAN X J Installation and oXOFShT manual JS DPPMFE heat pump outdoor VOJU 5 5...

Page 2: ...he installation and maintenance cost for the life cycle of the system The purpose of this manual is to provide you with information that is useful from reception of the equipment through installation...

Page 3: ...Manual Table 4 3 and Table 4 4 A indoor units standard cooling capacity in kW x 10 3 model identification For 1 outdoor unit connected to 1 indoor unit applications please consider the following instr...

Page 4: ...3DJH LQWHQWLRQDOO OHIW EODQN 06 1 0L 0 7...

Page 5: ...Installation manual 8 06 1 0L 0 7 QVWDOODWLRQ PDQXDO...

Page 6: ...3DJH LQWHQWLRQDOO OHIW EODQN 06 1 0L 0 7 QVWDOODWLRQ PDQXDO...

Page 7: ...connection device which has at least 3mm separation distance in all pole and a residual current device RCD with the rating of above 10mA shall be incorporated in the fixed wiring according to the nati...

Page 8: ...or more thickness for 15 9 Use copper pipe with 1 0 mm or more thickness for 19 0 Flare nut and flare works are also different form those of the conventional refrigerant take out the flare nut attache...

Page 9: ...e building and the air conditioner should comply with the regulation of National Electric Standard Install indoor unit outdoor unit power cord and connecting wire at least 1m away from TV set or radio...

Page 10: ...the outdoor unit pay attention to the installation place and the drainage pattern if it s installed at the alpine zone the frozen condensed water will block up the water outlet please pull out the rub...

Page 11: ...iquid pipe Branch Pipe 4 1 4 1 R410A Indoor unit connecting pipes diameters 1 R410A Indoor unit connecting pipes diameters 4 3 2 Example 1 In the Fig 4 5 The downstream inner units of the L2 and its t...

Page 12: ...ated When capacity of indoor unit greater than or equal to the sum of 120 in order to ensure the effectiveness of machine and then try to open the indoor units at different time When the capacity of i...

Page 13: ...increase the gas side main pipe size P N N P N N Inner branch pipes are a f the size selection please refers to Table4 6 Note The max length of the branch pipe should not longer than 15m Indoor unit...

Page 14: ...ded Using vacuum pump to do the vacuum never using refrigerant to expel the air Vacuuming should be done from both liquid side and gas side simultaneously Calculate the added refrigerant according to...

Page 15: ...unit Signal wire between indoor units 1 3 4 1 4 3 1 1 4 3 4 3 Branch Box Branch Box CCM Branch Box Please use 3 core shielded wire and connect the shielded layer to Grounding Power Supply Power Supply...

Page 16: ...oor Communication Bus Indoor Unit Indoor Unit wire distribution box Switch Circuit breaker Switch Circuit breaker Power wiring outdoor Central control monitor CCM CCM Computer in broken line table use...

Page 17: ...ts NOTE Single phase indoor unit Wire controller The reserved wire control function is indicated in broken line table users can purchase the wire controller when necessary In broken line table users c...

Page 18: ...er Explain the contents in the owner s manual to the customers in details Please press constraint cool button to carry out refrigerant recycling process Keep the low pressure above 0 2MPa other wise c...

Page 19: ...0wner s manual 6 8 06 1 0L 0 7 2ZQHU V PDQXDO...

Page 20: ...r outlet Fig 1 All the pictures in this manual are for explanation purpose only They may be slightly different from the air conditioner you purchased depend on model The actual shape shall prevail NOT...

Page 21: ...to the equipment Failure to observe a warning may result in death The appliance shall be installed in accordance with national wiring regulations Do not use the air conditioner for other purposes In o...

Page 22: ...y with the appliance When capacity of indoor unit greater than the sum of 100 capacity of indoor unit will be attenuated When capacity of indoor unit greater than or equal to the sum of 120 in order t...

Page 23: ...immediately Power comes again The lamp on the display panel of indoor unit flashes And then unit will auto restart Mishandling in operation If mishandling happens because of lighting or mobile wireles...

Page 24: ...ayed in the Control Panel Those Indoor Units which are running on Heating Mode will run continuously If the Air Conditioner Administrator has set running mode then the air conditioner can not run on m...

Page 25: ...real and the setting speed Typhoon protection Indoor evaporator hi tempprotection Low pressure protection Hi pressure protection Inverter module protection Compressor discharge protection temperature...

Page 26: ...ard when the system is in cooling operation or at a stop When the drain pump optional accessories is in operation this noise is heard A pishi pishi squeaking sound is heard when the system stops after...

Page 27: ...d indoor unit heat exchanger is dirty The air filter is dirty Inlet outlet of indoor outdoor units is blocked Doors and windows are open Sunlight directly shine Too much heat resource Outdoor temp is...

Page 28: ...k whether the signal transmitter of the remote controller is properly directed to the infrared signal receiver of the indoor unit when the ON OFF button is pressed Directly transmit the signal transmi...

Page 29: ...FSUJGJDBUJPOT 06 1 0L 0 7 2ZQHU V PDQXDO...

Page 30: ...Page intentionally left blank 06 1 0L 0 7 2ZQHU V PDQXDO...

Page 31: ...directive sur les machines directiva m quinas 2014 30 UE electromagnetic compatibility compatibilit elettromagnetica Elektromagnetische Vertr glichkeit compatibilit lectromagn tique compatibilidad el...

Page 32: ...l com CLIVET ESPA A S A U Service and Maintenance Division Calle Real de Burgos N 12 28860 Paracuellos del Jarama Madrid Espa a Tel 34 91 6658280 Fax 34 91 6657806 info clivet es CLIVET GmbH Hummelsb...

Page 33: ...SAN X J 5 5 Installation and oXOFShT manual JS DPPMFE IFBU QVNQ PVUEPPS VOJU...

Page 34: ...JPO BOE UIF JOTUBMMBUJPO BOE NBJOUFOBODF DPTU GPS UIF MJGF DZDMF PG UIF TZTUFN 5IF QVSQPTF PG UIJT NBOVBM JT UP QSPWJEF ZPV XJUI JOGPSNBUJPO UIBU JT VTFGVM GSPN SFDFQUJPO PG UIF FRVJQNFOU UISPVHI JOTU...

Page 35: ...or unit connected to 1 indoor unit applications please consider the following instructions Schematics refer to multiple indoor unit design for 1 to 1 application please consider the first indoor unit...

Page 36: ...1BHF JOUFOUJPOBMMZ MFGU CMBOL 0 0 1 06 1 0L 7 7...

Page 37: ...Installation manual 8 0 0 1 06 1 0L 7 7...

Page 38: ...1BHF JOUFOUJPOBMMZ MFGU CMBOL 0 0 1 06 1 0L 7 7...

Page 39: ...riate installation may result in water leakage electric shock or fire Turn off the main power supply switch or breaker before attempting any electrical work Make sure all power switches are off Failur...

Page 40: ...Copper pipe gauge adjusting projection margin 21 Vacuum pump adapter Required tools for installation work 1 Philips screw driver 2 Hole core drill 65mm 3 Spanner 4 Pipe cutter 5 Knife Refrigerant Pip...

Page 41: ...unit power cord and connecting wire at least 1m away from TV set or radio to prevent noise or picture interference Strong wind Strong wind 3 2 Installation space Unit mm 300 600 300 3000 Wall or obst...

Page 42: ...the frozen condensed water will block up the water outlet please pull out the rubber stopper of the reserve water outlet If that still fails to satisfy for the water draining please knock open the oth...

Page 43: ...ted to the indoor unit is at least 0 5m DV side mm Liquid si de mm 15 9 9 5 19 1 9 5 FQZHN 01D FQZHN 01D FQZHN 01D FQZHN 02D 19 1 9 5 22 2 9 5 22 2 9 5 FQZHN 02D FQZHN 02D 25 4 9 5 Main pipe size when...

Page 44: ...pe diameter of the connector in the outdoor unit s body Gas Side Liquid Side 20 22 4 26 When capacity of indoor unit greater than the sum of 100 capacity of indoor unit will be attenuated When capacit...

Page 45: ...as side main pipe size Inner branch pipes are a f the size selection please refers to Table4 6 Note The max length of the branch pipe should not longer than 15m Indoor unit branch pipe The main pipes...

Page 46: ...um pump to do the vacuum never using refrigerant to expel the air Vacuuming should be done from both liquid side and gas side simultaneously Calculate the added refrigerant according to the diameter a...

Page 47: ...of the outdoor unit P Q E L N P Q E L N P Q E L N P Q E L N B B C N A K2 K2 E O K1 K1 A E Y E P X Q E Power supply for the outdoor unit monitor Outdoor unit Outdoor unit monitor Optional L N L N K1 K2...

Page 48: ...able insert electric wires in their respective electric wire pipes and reserve a proper inter wire distance distance between power cables lower than 10 A 300 mm lower than 50 A 500 mm Use a three core...

Page 49: ...the insulation material or the condensing dew will be caused The air conditioners can connect with Central Control Monitor CCM Before operation please wiring correctly and set system address and netw...

Page 50: ...ease press constraint cool button to carry out refrigerant recycling process Keep the low pressure above 0 2MPa other wise compressor may be burnt out Fig 7 1 NOTE 7 1 Important information for the us...

Page 51: ...0wner s manual 6 8 0 0 1 06 1 0L 7 7...

Page 52: ...0 0 1 06 1 0L 7 7...

Page 53: ...or damage to the equipment Failure to observe a warning may result in death The appliance shall be installed in accordance with national wiring regulations Do not use the air conditioner for other pu...

Page 54: ...0 capacity of indoor unit will be attenuated When capacity of indoor unit greater than or equal to the sum of 120 in order to ensure the effectiveness of machine and then try to open the indoor units...

Page 55: ...lay panel of indoor unit flashes And then unit will auto restart Mishandling in operation If mishandling happens because of lighting or mobile wireless please shut off the manual power switch and turn...

Page 56: ...n 30 minutes 8 Voltage protection fault or a lack of Phase B Phase N E5 9 10 11 DC fan motor fault Discharge temperature sensor fault E6 EA E7 2 times of E6 protection in 10 minutes EB P0 HF E2 12 13...

Page 57: ...when the system is in cooling operation or at a stop When the drain pump optional accessories is in operation this noise is heard A pishi pishi squeaking sound is heard when the system stops after he...

Page 58: ...ndoor unit heat exchanger is dirty The air filter is dirty Inlet outlet of indoor outdoor units is blocked Doors and windows are open Sunlight directly shine Too much heat resource Outdoor temp is too...

Page 59: ...hether the signal transmitter of the remote controller is properly directed to the infrared signal receiver of the indoor unit when the ON OFF button is pressed Directly transmit the signal transmitte...

Page 60: ...BY JOGP DMJWFUDPNFSDJBM DPN CLIVET ESPA A S A U Service and Maintenance Division BMMF 3FBM EF VSHPT 1BSBDVFMMPT EFM BSBNB BESJE TQB B 5FM BY JOGP DMJWFU FT CLIVET GmbH VNNFMTC UUFMFS 4UFJOEBNN PSEFSTU...

Page 61: ...M 01 16 07 18 SAN X J 5 5 Installation and oXOFShT manual JS DPPMFE heat pump outdoor VOJU...

Page 62: ...he installation and maintenance cost for the life cycle of the system The purpose of this manual is to provide you with information that is useful from reception of the equipment through installation...

Page 63: ...ification For 1 outdoor unit connected to 1 indoor unit applications please consider the following instructions Schematics refer to multiple indoor unit design for 1 to 1 application please consider t...

Page 64: ...1BHF JOUFOUJPOBMMZ MFGU CMBOL 06 1 0L 7 7...

Page 65: ...Installation manual 8 06 1 0L 7 7...

Page 66: ...1BHF JOUFOUJPOBMMZ MFGU CMBOL 06 1 0L 7 7...

Page 67: ...reaker before attempting any electrical work Make sure all power switches are off Failure to do so may cause electric shock Connect the connecting cable correctly If the connecting cable is connected...

Page 68: ...e applied when welding copper pipes Fill nitrogen of 0 2kgf cm2 before welding Cut off nitrogen when the copper pipe completely cooled after welding 4 Heat preservation process should be applied to re...

Page 69: ...as If a combustible gas leaks and stays around the unit a fire may occur Remove obstacles around the unit in order to leave enough space for air circulation Install the unit near to the indoor unit as...

Page 70: ...it basement should be made in strong concrete ground See Fig 3 6 for common practice or start after field measurement The basement should be completely horizontal and make sure all the contactors can...

Page 71: ...efrigerant settings Names Main pipe Indoor unit main pipe Outdoor unit main pipe Indoor unit manifold components Piping position Pipe between the outdoor unit and indoor side first manifold Pipe which...

Page 72: ...ngle side air outlet 18 45 Single side air outlet 56 Low static pressure 18 45 Low static pressure 56 Thin duct 71 A5 Duct 22 45 A5 Duct 56 80 A5 Duct 90 140 12 7 Flare 15 9 Flare 12 7 Flare 15 9 Flar...

Page 73: ...inciple of maximum value it should apply FQZHN 03C 3 Main pipe please refer to Table 5 5 and Table 5 7 In Fig 5 5 main pipe L1 its outdoor unit capacity is 45kW Its gas liquid pipe diameter is 25 4 12...

Page 74: ...ndoor unit 5 6 Remove Dirt or Water in the Pipe 1 Make sure there is no any dirt or water before connecting the pipe to the outdoor units 2 Wash the pipe with high pressure nitrogen never use refriger...

Page 75: ...efrigerant leakage after fastening the bonnet Prepare a hexagonal wrench specification 6mm Open approach 1 Insert a hexagonal wrench into the valve rod and spin anticlockwise 2 When the valve rod can...

Page 76: ...branch circuit Please put the connective wire system between indoor unit and outdoor unit with the refrigerant system together Use 3 core shielded wire as indoor unit and outdoor unit signal wire The...

Page 77: ...19 20 21 22 22 23 23 24 24 25 25 30 30 31 28 29 30 30 27 26 6 3 Outdoor unit main control board Outdoor address dial switch Outdoor power dial switch Quantity setting dial switch of indoor units Cons...

Page 78: ...or system high pressure inspection Reserved Reserved Reserved Control port of DC fan A Control port of DC fan B Inspection port for outdoor ambient temp and condensator coil Current inspection port of...

Page 79: ...lized duplexure and should install RCCB and manual switch 3 Power supply RCCB and manual switch used for a same indoor unit should have universality Indoor unit power supply for the same unit should u...

Page 80: ...l Outdoor power supply Switch Fuse Power supply of indoor unit centralized controller Indoor unit centralized controller Optional Power supply of Digital electric meter Optional Fuse Indoor unit Indoo...

Page 81: ...places easily keep refrigerant b Leak alarm related to mechanical ventilator 8 TEST RUNNING 8 1 Check points before test running 1 If indoor and outdoor units have been installed properly 2 Whether pi...

Page 82: ...f there s vibration and abnormal noise when operating Test if heating function works normally for heating and cooling A C 2 Outdoor unit If there s vibration and abnormal noise when operating Whether...

Page 83: ...0wner s manual 6 8 06 1 0L 7 7...

Page 84: ...06 1 0L 7 7 1BHF JOUFOUJPOBMMZ MFGU CMBOL...

Page 85: ...njury or damage to the equipment Failure to observe a warning may result in death The appliance shall be installed in accordance with national wiring regulations Do not use the air conditioner for oth...

Page 86: ...ence and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved children should not play with This appliance Cle...

Page 87: ...it address Outdoor unit itself capacity Moduler outdoor unit Qty Qty setting of indoor units Total capacity of outdoor unit Total requirement of indoor unit capacity Total requirement of main unit cor...

Page 88: ...on the air inlet or air outlet of outdoor unit is blocked Strong wind is continuously blowing to the air outlet of the outdoor unit Under heating operation too much dust and rubbish adhere to the dust...

Page 89: ...B X represents in which system 1 is system A 2 is system B COMM Error between IR341 and main chip COMM Error between 0537 and main chip 3 times of P6 protection in 60 munites X represents in which sys...

Page 90: ...to avoid super hot in the components 2 For detailed information about cleaning please refer to Indoor unit operation manual 4 5 Maintenance After leaving unused for a long time inspect the air inlet...

Page 91: ...1BHF JOUFOUJPOBMMZ MFGU CMBOL...

Page 92: ...l com CLIVET ESPA A S A U Service and Maintenance Division Calle Real de Burgos N 12 28860 Paracuellos del Jarama Madrid Espa a Tel 34 91 6658280 Fax 34 91 6657806 info clivet es CLIVET GmbH Hummelsb...

Reviews: