Electrical input of the fan
Pressure drops of optional components
The value of static pressure available on the supply and return duct is obtained by subtracting from the available net maximum pressure (see general table
of technical data) the pressure drops of any accessories.
Size
70
120
200
300
500
650
EHPCX - Preheating electric heaters from 0.7 kW
Pa
7
9
-
-
-
-
EHPCX - Preheating electric heaters from 1.5 kW
Pa
-
-
3
5
7
9
EHPCX - Preheating electric heaters from 3 kW
Pa
-
-
3
5
7
9
HSE3MX/HSE3LX - Electrode boiler steam humidifier from 3 kg/h
Pa
-
-
-
-
-
-
FES/FESX - Electronic filter
1
Pa
-8
-12
-7
-11
-6
-10
FAEX - Exaust air filter
2
Pa
-
-
9
15
11
18
The values shown are to be considered approximate for units operating power in normal use with standard air flow rate.
1. Pressure drop differences compared to standard G3 pleated filters
2. Pressure drops with filters with average dirtiness
Electrical input of the single fan in conditions of standard flow in heating.
•
outdoor air 7° C
•
return 20°C 50%