16.14 List of the parameters accessible by the thermostat
Par
Description
range
UM
Def.
P01
BandaLavoro:
Working band
0 ÷ 15.0
°C
2.0
P02
MaxH2Ocool:
Water max. temperature for cooling operating
0 ÷ 30.0
°C
20.0
P03
MinH2OHeat:
Water min. temperature for heating operating
0 ÷ 40.0
°C
30.0
P05
TimeOnPeriodical
Defines the duration of the OFF phase of the periodical
0 ÷ 999
min
2
P06
TempoOffPeriodica
0 ÷ 999
min
5
Defines the duration of the OFF phase of the periodical
P10
OffsetEco
0 ÷ 4.0
°C
3.0
P11
SetUrHeat:
Heat UR set point
30 ÷ 70
%
50
P12
BandUrHeat:
Intervention band of the heat humidifier
0 ÷ 10
%
5
P21
FanOffCool:
Fan status at “cooling” thermoregulator, satisfied
0: stop, 1: continuous, 2: periodical
0…2
num.
2
P22
FanOffHeat:
Fan status at “heating” thermoregulator, satisfied
0: stop, 1: continuous, 2: periodical
0...2
num
0
P31
ModoAuto:
It enables the automatic saison change
0: Manual, 1: Auto
0…1
flag
0
P41
BT1 probe calibration
-9.9+10.0
°C
0.0
P42
BT2 probe calibration
-9.9+10.0
°C
0.0
P43
Thermostat temp. probe calibration
-9.9+10.0
°C
0.0
P44
Thermostat UR probe calibration
-9.9+10.0
%UR
S01
TESToperativa
°C
S02
TH2Ooperativa
°C
S03
TARIAoperativa
°C
S04
URoperativa
Hr%
S05
ActualMode
bitmap
S06
CurrentSetpoint
°C
S07
Current humidity Set
Hr%
S08
Errors
bitmap
S09
Active humidifcation
flag
S10
Active dehumidification
flag
S11
FanStatus:
0: off, 1: on
0…1
flag
S12
Actual fan:
0-7 if motor 0-10 V
0-3 if 3 speed motor
0-1 if single-speed motor
0…7
num.