1
Unscrew the 6 Ø 3.9x9.5 screws “A” (3 left side + 3 right side).
Remove the panel, moving it in the direction of the arrow “B”.
2
Unscrew the 4 Ø 3.9x9.5 screws “C” (2 left side + 2 right side).
Slightly incline the main drain pan towards the arrow “D” and move it away from the left
-hand shoulder in the
direction of the arrow “E”.
3
Unscrew the 4 Ø 3.9x9.5 screws “F” supporting the coil from the shoulders (2 left side + 2 right side).
Slightly incline the coil towards the arrow “G” and move it away from the left
-hand shoulder in the direction of the
arrow “H”.
4
Open the 2 pre-punched holes arranged on the opposite shoulder and corresponding to the coil hydraulic
connections “I”.
Open the pre-
punched hole arranged on the opposite shoulder and corresponding to the drain pipe “L”.
5
Reverse the direction of the coil from pos. “M” to pos. “N” (rotation 180°).
6
Reverse the direction of the drain pan from pos. “O” to pos. “P” (rotation 180°).
REVERSING THE HYDRAULIC CONNECTIONS
Compulsory for vertical units only:
Place the electric cables on the opposite side to that of the definitive hydraulic connections.
If the terminal board is mounted (or electric board or electronic cards), remove it and mount on the opposite side .
Reinstall the component retracing the procedure used for the disassembly.
Reinstall the component on the opposite side, accordingly (in mirrored and symmetrical way) to the original one.