9 - TROUBLESHOOTING
WATER DRAGGED THROUGH THE ELIMINATOR
Excessive air flow-rate
Excessive water flow-rate to the humidifier
Defective seal on the eliminator
INSUFFICIENT HUMIDIFICATION
Dirty water filter
Dirty nozzles
Deposits in the wet deck
Insufficient water level in the tank, due to defective control by
the float or accidental leaks
POOR COIL HEATING CAPACITY
Insufficient temperature or flow-rate of the thermal carrier fluid
Reduced air flow-rate
Air in the coil. Vent.
Automatic control malfunctioning
Condensate discharge malfunctioning (steam coils)
EXCESSIVE NOISE
Slipping of the belts
Defective bearings
Magnetic howling of the motor due to a voltage drop or
manufacturing defect
Foreign material in the fan shroud
Vibration of the damper fins
Howling due to vibration of the ducts, baffles, outlets, diffusers
Loosening of the wheel on the shaft
Loose fan cut-off
Loose motor cooling fan
Excessive air flow-rate