background image

22

 

7 - START-UP

 

 

Check that the cartridges containing the carbon are correctly 

inserted and check the operation of the air seal gasket. 

Upon request, a differential pressure gauge can be supplied to 

fit to the pre-filter, bag filter and absolute filter sections.  

A differential pressure switch, visual or audible, can also be 

supplied for the same purpose. 

The rotary filter is supplied as standard with a differential 

pressure switch. 

Remove any safety locking devices from the fan assembly, 

leaving the shock absorbers in operation. 

Check the alignment of the pulley and the tension of the belts 

(see "Maintenance"). 

Check the correct direction of rotation of the fan, in reference 

to the arrow applied. 

Check that the operation of the fan assembly is free of 

vibrations. If not, carefully check the assembly. 

Check that, after the first hour of operation, the temperature of 

the fan supports does not exceed 60°C. 

Measure the effective power input of the motor and compare it 

against the rated value. If the input of the motor is too high, 

above the rating, or alternatively is less than envisaged, check 

the pressure drops in the system circuits.  

High power inputs indicate, especially for fans with forward 

blades, an excessive volume of air due to lower resistance in 

the circuit, and thus the overloading of the electric motor.  

Vice-versa, low input indicates poor air flow due to higher 

pressure drops than envisaged.  

To normalise the system, adjust the transmission to vary the 

speed of the fan. In no circumstances, in fact, are such 

problems due to the fans, as these are built in series, 

extensively tested, and their typical curves are to be 

considered accurate (except for the max. deviation of 5%, as 

declared by the manufacturer). The precise calculation of the 

pressure drops in the entire circuit is thus essential, so as to 

prevent the above problems. 

START-UP REPORT

 

 

To detect the objective operational conditions is useful to 

control the unit over time. 

With the unit running, meaning in stable conditions and near 

the work ones, detect the following data:  

 

Overall absorptions and voltages with unit in full load 

 

Absorptions of the various electric loads  

 

Temperatures and flow rates of the various fluids 

(water, air) at input and output of the unit 

The detections must be kept and made available during 

maintenance interventions.

 

 

Check the air and water temperatures are within the operatio-

nal limits. 

Start the unit; refer to the "Adjustment" section for indications 

on the control system. 

With the unit running, meaning in stable conditions and near 

the work ones, check:  

 

power supply voltage 

 

unit overall absorption 

 

absorption of the individual electric loads. 

VOLTAGES

 

 

ACTIVATED CARBON FILTERS 

DIRTY FILTER DETECTION DEVICE 

FAN 

Summary of Contents for AQX CLA Series

Page 1: ...Installation use and maintenance manual AQX CLA 1 32 Modular air handling units MU14B006GB 01 19 01 2015...

Page 2: ...im is that to offer its customers developed systems that assure the best comfort reduce energy consumptions and installation and maintenance costs for the entire life span of the system With this manu...

Page 3: ...connections 15 6 Electric connections 16 7 Start up 20 8 Maintenance 23 9 Troubleshooting 27 10 Technical information 29 11 Disposal 30 12 Residue risks 31 TABLE OF CONTENTS The data contained in this...

Page 4: ...ety standards Periodical checks Carry out periodical checks to identify any loose damaged or broken parts The lack in repair entails the risk of damages to things and personal injuries Fault Malfuncti...

Page 5: ...xxxxxx the year of manufacture the wiring diagram number electrical data manufacturer logo and address Serial number Unambiguously identifies each machine Enables identifying the specific spare parts...

Page 6: ...t document and write the wording Collection with reserve for evident shortages damages due to transport notices via fax and with registered letter with acknowledgement receipt to carrier and supplier...

Page 7: ...accumulating obstructing the coils Avoid places that may be subject to floodings Install the unit lifted from the ground Protect the unit with suitable fence in order to avoid access to unauthorised...

Page 8: ...Special attention should be paid when fitting the gasket use silicon to ensure a perfect seal where required 1 Joint protection ABS 2 Roof 4 Aluminium frame 5 Base 6 Waterproofing 7 Support base 4 5 6...

Page 9: ...t the gaskets and the silicon seals prevent the by pass of air Check that the air by pass damper if present is working perfectly so as to ensure complete closing 3 5 HEAT RECOVERY UNITS STATIC CROSS F...

Page 10: ...nd exit of the main elements facilitate inspection and maintenance AN AIR BLEED VALVE installed in all of the highest points of the system allowing the venting of the circuits air DRAINAGE TAPS instal...

Page 11: ...vertical pipes When connecting to the supply mains refer to the previous precautions and comments In order to avoid damage to the coil water hammer special attention should be paid to the sizing and t...

Page 12: ...level of water is around 15mm below the overflow Check after 5 minutes of operation that the wet deck is completely wet When new the wet deck will release foam for a short time only The evaporation o...

Page 13: ...ct traps will cause air to flow up through the drain and thus make it difficult to discharge the condensate which as a result will overflow into the adjacent sections and leak from the air conditioner...

Page 14: ...hus incorrect draining of the tank p H S T p pressure in the tank being drained in mm wc 1 mm wc 9 81 Pa T vertical distance between the lower edge of the tank drain and the upper edge of the first lo...

Page 15: ...e air Thermally isolate the channels and the flanges to avoid energy losses and forming of condensation DIFFUSERS INLETS GRILLES A correct diffusion of the air in the room is determining for the level...

Page 16: ...cable and signal Lay the cables away from the power lines with different voltage or that emit interferences of electromagnetic origin Avoid laying the cables near the equipment that can create electr...

Page 17: ...upply terminal Y to X and to Z star connection Operation terminals U V W to the three phase supply terminal U to Z V to X and W to Z delta connection Single start with switch Dahlander Switch connecti...

Page 18: ...42 80 22 44 180 L 10 16 40 52 100 30 59 200 L 16 25 52 65 125 37 71 225 S 25 35 60 75 160 45 86 225 M 35 50 72 100 200 55 104 250 M 50 70 72 100 200 75 144 280 S 70 120 102 170 250 90 172 280 M 95 150...

Page 19: ...Check the power input 6 9 SPRAY NOZZLE HUMIDIFICATION Check the mains have features conform with the data reported on the matriculation plate Connect the electric pump to the mains power supply using...

Page 20: ...the limits can entail irreversible damages L1 L2 L3 388V 379V 377V 388 379 377 3 381 A MAX A 388 381 7 S 7 A x 100 1 83 OK 1 2 3 Only with hot water coil humidifier options 1 Find out if before connec...

Page 21: ...s enclosed a complete series of documents inside the filter electrical panel including wiring diagrams instructions for connections to the equipment etc Caution the bag filters absolute or activated c...

Page 22: ...e circuit and thus the overloading of the electric motor Vice versa low input indicates poor air flow due to higher pressure drops than envisaged To normalise the system adjust the transmission to var...

Page 23: ...erstandings and be able to use the system when required 8 4 Stand by i i 8 5 DAMPERS Extruded aluminium with nylon gears This type of damper does not require lubrication but simply normal cleaning as...

Page 24: ...nium stainless steel The counter frame is fitted with a gasket glued to the lip of the filter support so as to ensure perfect air tightness and prevent any by pass The filtering cell is fastened to th...

Page 25: ...t using steel pins for the holes Wash the inside of the tank and the various components The wet decks must be fitted in the exact correct position in the humidifier The air and water flow in a specifi...

Page 26: ...The deterioration of the bearings is signalled by an increase in noise and the overheating of the bearings with the release of liquid grease 8 18 PULLEYS The transmission pulleys are fitted to the sh...

Page 27: ...hroud Vibration of the damper fins Howling due to vibration of the ducts baffles outlets diffusers Fan pumping excessive back pressure in respect to the flow rate Excessive air flow rate POOR COIL HEA...

Page 28: ...PACITY Insufficient temperature or flow rate of the thermal carrier fluid Reduced air flow rate Air in the coil Vent Automatic control malfunctioning Condensate discharge malfunctioning steam coils EX...

Page 29: ...anical strength of the casing D1 D1 Air tightness of casing 400 Pa L1 L2 Air tightness of casing 700 Pa L1 L2 Filter bypass F9 F9 Transfer factor T2 T3 Heat bridge factor TB3 TB3 Frequency Hz 125 250...

Page 30: ...in the residue risks section If necessary additional information to that listed below can be requested from the manufacturer distributor importer as responsible for the collection treatment of waste d...

Page 31: ...g the correct fastening of all fastening screws of the panelling can cause damages to things persons or the unit itself Periodically check closing of all panels and their correct fastening In the even...

Page 32: ...info clivetcomercial com CLIVET ESPA A S A U Service and Maintenance Division Calle Real de Burgos N 12 28860 Paracuellos del Jarama Madrid Espa a Tel 34 91 6658280 Fax 34 91 6657806 info clivet es CL...

Reviews: