If the joint is taken out, which fixes the lever
with the chainlet, take care in assembling it
again in the same position.
After having placed the knob at 60°C, block
the lever with the chainlet in a slightly incli-
ned position downwards, so that the chain-
let will be in axis with the air gate damper.
For the adjustment of the “REGULUS RT2”,
which essentially consists in the determina-
tion of the chainlet length, proceed in the fol-
lowing way:
– Place the knob at 60°C.
– Switch on the boiler with opened air gate
damper.
– When the water temperature of 60° C
is reached in the boiler, fix the chainlet in
such a way on the lever of the air gate
damper, in order to obtain an opening of
about 1 mm.
– Now the regulator is calibrated and it is
possible to choose the desired operating
temperature by rotating the knob.
Fig. 7
Fig. 10
2.8
HYDRAULIC CONNECTION DIAGRAM
2.8.1
Open expansion tank system
VE
VS
VM
PI
IR
VR
SOLIDA
LEGEND
VE
Open expansion tank
VS
System safety valve 3 BAR - 1/2”
VM Mixing valve
VR Check valve
PI System pump
IR Heating system
GG SF