23
1.3
TECHNICAL FEATURES
GG E
3
4
5
6
7
Output
Minimum
kW
18,9
24,5
32,5
41,7
49,9
Maximum
kW
23,5
31,3
40,0
48,1
57,5
Input
Minimum
kW
21,1
27,2
36,0
46,1
55,0
Maximum
kW
26,2
34,8
44,3
53,1
63,3
Sections
n°
3
4
5
6
7
Maximum water head
bar
4
4
4
4
4
Water content
l
12,8
16,8
20,8
24,8
28,8
Smokes loss of head
Minimum/Maximum
mbar
0,05/0,11
0,12/0,16
0,15/0,21
0,30/0,35
0,32/0,43
Water loss of head*
mbar
5
10
15
20
25
Combustion chamber pressure
mbar
–0,02
–0,02
–0,02
–0,02
–0,02
Suggested chimney depression
mbar
0,07/0,13
0,14/0,18
0,17/0,23
0,32/0,37
0,34/0,45
Smokes temperature
Minimum/Maximum
°C
160/185
160/185
160/185
160/170
160/170
Smokes flow
Minimum/Maximum
m
3
n/h
24,0/31,6
32,4/41,4
42,9/52,8
54,8/63,3
65,5/73,8
Smokes volume
dm
3
9
12
15
18
21
CO
2
%
12,5
12,5
12,5
12,5
12,5
C.H. adjustment range
°C
30÷85
30÷85
30÷85
30÷85
30÷85
Weight
kg
109
135
161
186
212
* With
∆
t 10°C
GG E technical features - NOx: Class 3 (Burner with low polluting emissions)
3
4
5
6
7
Output
Minimum
kW
–
18,0
27,5
36,2
45,0
Maximum
kW
19,7
27,6
32,8
45,7
55,1
Input
Minimum
kW
–
20,0
30,5
40,0
49,6
Maximum
kW
21,9
30,7
36,3
50,5
60,7
Sections
n°
3
4
5
6
7
Maximum water head
bar
4
4
4
4
4
Water content
l
12,8
16,8
20,8
24,8
28,8
Pérdidas de carga lado humos
Minimum
mbar
–
0,04
0,08
0,20
0,22
Maximum
mbar
0,06
0,07
0,13
0,31
0,44
Water loss of head (
∆
t 10°C)
mbar
5
10
15
20
25
Combustion chamber pressure
mbar
–0,02
–0,02
–0,02
–0,02
–0,02
Suggested chimney depression
Minimum
mbar
–
0,06
0,10
0,22
0,24
Maximum
mbar
0,08
0,09
0,15
0,33
0,46
Smokes temperature
Minimum
°C
–
110
130
140
155
Maximum
°C
140
145
145
155
180
Smokes flow
Minimum
m
3
n/h
–
24,3
36,8
48,7
59,5
Maximum
m
3
n/h
26,8
37,4
43,9
61,5
72,8
Smokes volume
dm
3
9
12
15
18
21
CO
2
%
12,8
12,8
12,9
12,8
13,0
C.H. adjustment range
°C
30÷85
30÷85
30÷85
30÷85
30÷85
Weight
kg
109
135
161
186
212
Summary of Contents for GG E 3
Page 1: ...GG E 3 7 Cod 6276052A 07 2019 IT ES ENG FR RUS ...
Page 5: ...3 1 4 PERDITE DI CARICO CIRCUITO CALDAIA Fig 2 GG E 7 GG E 6 GG E 5 GG E 4 GG E 3 ...
Page 12: ...10 NOTE ...
Page 26: ...24 1 4 LOSS OF HEAD Fig 2 Loss of head mbar Flow l h GG E 7 GG E 6 GG E 5 GG E 4 GG E 3 ...
Page 36: ...24 1 4 LOSS OF HEAD Fig 2 Loss of head mbar Flow l h GG E 7 GG E 6 GG E 5 GG E 4 GG E 3 ...
Page 63: ...51 NOTE ...
Page 64: ...52 NOTE ...
Page 65: ......
Page 66: ...Via Garbo 27 37045 Legnago Vr Tel 39 0442 631111 Fax 39 0442 631292 ...