Adjustment
According to the pressures for the air and water adjustment, the
quality of the fogging can be substantially altered.
It is important to comply, precisely with the following pressures:
- Air:
5 bar
minimum
- Water:
0.4 bar
maximum
Blowing duct
As standard, ModulAir air conditioners are provided with a blowing grill, placed each
fan. This grill protects the fan propeller and limits the turbulence of the air stream projected.
The combined effects of the angle of the fan, the tubular rings of the directive grill and the
bearing capacity of the ceiling, provide an even distribution of the blown air.
However certain applications or configurations require the use of a textile duct.
This duct is connected to the ferrule of the fan and replaces the grill.
A textile duct is fragile to friction. During installation, make sure that it is perfectly free
on the suspension cables, that it does not chafe against a wall or any obstacle and that it
does not nip at the end of thereof. Otherwise there will be premature wear and the duct will
be torn.
In light of the low water pressure, the pressure head is to be taken
into consideration:
A difference of 39.37 inches in height between the level of the
control pressure gauge and the level of the nozzle is equal to a
pressure difference of 0.1 bar.
-
If the pressure gauge is placed at the level of the nozzle, no
correction.
-
If the pressure gauge is placed above the nozzle, subtract 0.1
bar per 39.37 inches.
-
If the pressure gauge is placed below the nozzle, add 0.1 per
39.37 inches.