background image

12

CLIMIA

Press the power key once to switch 
on the unit. 

If the units are inactive for long 
periods, disconnect them from the 
mains power supply.

Empty the condensate container 
completely and dry with a clean 
cloth.  

Beware of dripping condensate!

 

The units must be cleaned and 
dried completely before storing.

When storing the unit, cover with 
a plastic sheet/foil if necessary 
and store in an upright position 
in a sheltered and dry location.

The units are only permitted to be 
stored upright in a suitable storage 
location that is protected against 
dust and direct sunlight. 

Continuous operation with 

external condensate outlet

 

The units are equipped with a 
special connection nozzle on the 
rear. 
A standard 1/2” water hose can be 
connected to this. 

1. The condensate hose connection 
must be switched off first for this 
purpose. The rubber stopper can 
then be removed. 

2. Pull the condensate hose 
connection over a sufficiently long 
and suitable drain hose.

3. Connect the drain hose to the 
connection nozzles and tighten the 
condensate hose connection by 
hand. 

In unattended permanent operating 
mode, the condensate should 
preferably be drained into a lower-
level drain.  
If using an external collection 
container (pan, bucket, etc.), 
the unit must be placed at a correct 
height.

10.0 Shutdown

The units are equipped with four 
foot rollers and two additional 
handles for easy and convenient 
transport. 

   Before each change of location, 

switch off the unit and remove 
the power plug from the mains 
socket

   Empty the condensate bucket 

completely.

 

   If residual moisture remains on 

the evaporator or water remains 
in the condensate container, the 
units must only be transported in 
an upright position

   The transport rollers are only 

suitable for use on level and 
smooth ground

   The units must be carried when 

transporting on rough terrain or 
uneven surfaces

11.0 Unit transport

CAUTION!

There is no unit overflow 

protection in this variant.

CAUTION!

Ensure that the drainage hose is 

placed at an incline to the drain 

to allow the condensate to drain 

without hindrance! 

NOTE

Beware of dripping condensate. 

After switching off the units, the 

evaporator may continue to 

defrost under the influence of the 

ambient temperature. 

CAUTION!

The mains cable must never 

be used as a pull cord or fixing 

device.

Summary of Contents for CTK 240

Page 1: ...CLIMIA CTK 240 mobile air dehumidifier Operating manual Edition 1 0 English ...

Page 2: ......

Page 3: ...ted for errors or misprints 1 0 Safety instructions 4 2 0 Environmental protection and recycling 4 3 0 Guarantee 4 4 0 Intended use 4 5 0 Transport and packaging 5 6 0 Air dehumidification 5 7 7 0 Unit description 8 8 0 Set up 9 9 0 Commissioning 9 12 10 0 Shutdown 12 11 0 Unit transport 12 12 0 Care and maintenance 13 14 13 0 Troubleshooting and customer service 14 14 0 Electrical wiring 15 15 0 ...

Page 4: ...right water will escape otherwise Before each change of location the condensate container must be emptied All electrical cables on the outside of the units must be protected against damage e g by animals etc Before each change of location the condensate containers must be emptied Appropriate hazard prevention measures must be taken to prevent risks to people when performing installation repair mai...

Page 5: ...r materials such as powdery substances packaging wood and electronic units Buildings may be dried in a variety of ways 1 By heating and air exchange The air in the room is heated in order for moisture to be removed and then this air is fed outside All of the energy that is involved is lost together with the moist air that is released 2 By air dehumidification The moist air that is present within a...

Page 6: ...he temperature rises I e the maximum possible absolute water content becomes greater as the temperature rises Building materials and structures are capable of absorbing considerable volumes of water such as brick 90 190 l m heavy concrete 140 190 l m and limestone 180 270 l m The drying of moist materials such as masonry is effected as follows The moisture moves from the inside of the material to ...

Page 7: ...ensation heat The Energy transferred to the air from the condenser consists of 1 The amount of heat derived beforehand in the evaporator 2 The electrical drive energy 3 The condensation heat released by liquefying the water vapour Energy must be supplied when liquid is converted into a gas This energy is designated as evaporation heat It does not cause any increase in temperature but is required t...

Page 8: ...and discharged back into the room via the outlet grill with a temperature increase of around 5 10 C above the room temperature The processed dry air then re mixes with the room air Continuous circulation of the room air through the unit gradually reduces the relative humidity RH in the room to the desired humidity level Depending on the room air temperature and the relative humidity condensed wate...

Page 9: ... up instructions Min 0 5 m distance to wall Maintain adequate clearance from heaters or other sources of heat Keep windows and doors closed Fig 2 Schematic depiction of how to set up the air dehumidifier 9 0 Commissioning Before commissioning the unit or if local requirements dictate the air inlet grill and air outlet grill must be checked for contamination Important notes prior to commissioning A...

Page 10: ... of the unit can no longer be guaranteed NOTE After setting the required air humidity the display shows this for another 10 seconds before displaying the current air humidity again NOTE Note that the compressor does not switch on until a waiting time of 3 minutes has elapsed Restart protection Control panel The control panel contains various keys indicator lights and a display 7 The bucket full in...

Page 11: ...r function Pressing the timer key switches the unit s automatic mode on and off If automatic mode is switched off the arrow keys can be used to set the required operating time The operating time can be set for a maximum of 24 hours in increments of an hour The unit will switch itself off automatically after the set time has elapsed NOTE If the room temperature is sufficiently high 12 C the surface...

Page 12: ...e connection by hand In unattended permanent operating mode the condensate should preferably be drained into a lower level drain If using an external collection container pan bucket etc the unit must be placed at a correct height 10 0 Shutdown The units are equipped with four foot rollers and two additional handles for easy and convenient transport Before each change of location switch off the uni...

Page 13: ... traps with hose connection the fan and the fan housing carefully Check all unit components for damage and repair if necessary Carefully refit all parts that were removed in reverse order NOTE Regular care and maintenance is fundamental to a long service life and fault free operation of the unit CAUTION Before undertaking any work on the units the power plug must be removed from the mains socket N...

Page 14: ...the connection nozzles checked to see whether there are dirt deposits on them This work requires the unit to be opened and must therefore only be carried out by an authorised specialist company NOTE Heavily contaminated or damaged air filters must be replaced with new parts Only original spare parts may be used NOTE Adjustment and maintenance work may only be carried out by authorised and qualifie...

Page 15: ... in fully unreeled or reeled off condition NOTE The electrical connection to the units must be made at feedpoints with residual current devices in accordance with VDE 0100 Section 704 When installing the units in extremely damp environments such as laundry rooms showers etc the unit must secured with a residual current device provided by the customer in accordance with the regulations 14 0 Electri...

Page 16: ...iew of unit We reserve the right to modify the dimensions and design as part of the ongoing technical development process 2 1 4 3 5 6 7 8 10 11 12 37 3 32 31 30 26 47 45 44 43 41 39 38 49 50 51 9 46 40 42 16 33 21 13 23 24 22 ...

Page 17: ...Capillary 12 Y pipe 13 Condenser for compressor complete 16 Microswitch 21 Condensate trap cover 22 Fan housing 23 Fan wheel 24 Fan motor 26 Distribution block 30 Control board 31 Conductor board board 32 Probe evaporator EVAP 33 Hygrostat 34 Condenser fan motor 37 Mains cable with plug 38 Front wall 39 Back wall 40 Transport handle 41 Top cover 42 Intake grill 43 Air filter 44 Condensate bucket c...

Page 18: ... 27 C 60 RH l day 18 Fan stages 2 Max airflow volume m3 h 240 186 Condensate container capacity Litres 6 3 Refrigerant 1 R134A Refrigerant quantity g 200 Power supply V Hz 230 1 50 Max rated current consumption A 4 1 Max power consumption kW 0 57 Sound pressure level LpA 1m 2 dB A 46 41 Dimensions Depth mm 272 Width mm 384 Height mm 610 Weight kg 17 We reserve the right to modify the dimensions an...

Page 19: ...r cleaned Fan function checked Air inlet grid with filter cleaned Unit checked for damage Safety devices checked All fastening screws checked Electrical safety check Test run 1 Date Signature 2 Date Signature 3 Date Signature 4 Date Signature 5 Date Signature 6 Date Signature 7 Date Signature 8 Date Signature 9 Date Signature 10 Date Signature 11 Date Signature 12 Date Signature 13 Date Signature ...

Page 20: ... D 32758 Detmold Germany Name of the CE representative Intakt GmbH Climia Air conditioning and heating technology Niemeierstraße 13 D 32758 Detmold Germany Unit machinery model Air dehumidifier Series Class CLIMIA CTK 240 Series Class Number 1803 Delegated regulations EU 2011 65 EU 2011 2014 30 EU 2014 2014 35 EU 2014 Applicable standards DIN EN 12102 1 2018 DIN EN 55014 1 2017 DIN EN 55014 2 2015...

Page 21: ...21 CTK 240 mobile air dehumidifier Notes ...

Page 22: ...22 CLIMIA ...

Page 23: ...23 CTK 240 mobile air dehumidifier ...

Page 24: ...Intakt GmbH Climia Klima und Wärmetechnik Niemeierstraße 13 D 32758 Detmold ...

Reviews: