background image

Skuttle

®

 Model 592-22 

Power-Spray Humidifier 

24-Volt 

 

 

IMPORTANT:  

THIS HUMIDIFIER MUST BE INSTALLED BY A QUALIFIED CONTRACTOR. 

DO NOT INSTALL ON ANY SYSTEM WITH WATER PRESSURE  

LESS THAN 40 P.S.I. 

Installation on water systems with hardness ratings greater than 7 grains 

is not recommended. Such installations can result in nozzle blockage, 

dripping, erratic spray patterns and other maintenance problems.       

Hardness above 7 grains will also produce dust from solids in the water 

supply, which will be distributed throughout the home. Consult your     

municipal water provider before continuing. 

SAFETY PRECAUTIONS 

READ THESE PRECAUTIONS AND ALL INSTALLATION INSTRUCTIONS 

BEFORE INSTALLING THE HUMIDIFIER.  

NOTE: 

Skuttle Mfg. Co. assumes no responsibility under warranty  

if installer does not follow these instructions and safety precautions. 

Do not install a humidifier where the heating temperatures can exceed 200°F. 
Excessive  temperatures  will  harm  the  humidifier,  possibly  causing  water 
damage to the home.   
Do not install a humidifier where the surrounding temperature can be 32°F 
or  colder.  Frozen  water  will  damage  the  humidifier  and  burst  the  supply 
pipe, resulting in home damage.  

Do  not  cut  or  drill into  any  air  conditioning  or  electrical  accessories  during 
humidifier installation. 

DANGER:  Electrocution  is  possible  if  you  come 

in contact with a live wire; blindness can occur if refrigerant contacts 
your eyes. 

 

When  the  humidifier  is  installed  in  an  area  where  water  damage  could    
occur, connect the humidifier’s overflow provision to a suitable drain pan.  
For above-ceiling installations, always install a drain safety pan, plumbed to 
a suitable drain.  

For  initial  recommended  humidistat  settings,  refer  to  Table  1,  below.  (Be-
cause  relative  humidity  affects  people  differently,  these  settings  can  be 
raised or lowered slightly to suit personal comfort levels.) 

CAUTION:  Setting  the  humidistat  higher  than  the  recommended  set-
ting  can  cause  condensation,  resulting  in  home  damage. 

If excessive 

moisture  appears  on  windows  or  walls,  reduce  the  humidistat’s  humidity 
setting enough to eliminate condensation. If the situation continues, turn off 
the humidifier’s water source until condensation is gone.  
Make  sure  the  installation,  wiring  and  plumbing  of  the  humidifier  comply 
with local codes, ordinances and regulations.  

INSTRUCTIONS 

IMPORTANT:  This  product  should  not  be  used  in  conjunction  with  heat 
pump  systems. 

For  heat  pumps,  select  Skuttle  Model  592-9,  or  upgrade  to 

Models 55UD, 86UD, or a 60-series steam humidifier.  

GENERAL INFORMATION:  

1.0  This humidifier puts moisture into the home by spraying a fine mist of water 
into the warm air plenum, which is carried into the living area by the duct system.  
1.1    When  wired  as  recommended,  the  humidifier  will  operate  only  when  the 
furnace blower is in operation and the humidistat is calling for humidity.  
1.2  The nozzle capacity (flow) is rated at 40 P.S.I. This capacity varies accord-
ing to line pressure, as shown in Table 2, below.  

  

EXAMPLE: 

A home which requires .50 gallons of water per hour for proper humidifica-

tion, and which has a water pressure of 80 P.S.I., would need a .37 nozzle to do the job. 

1.3  If the water pressure is excessive, a pressure regulator valve will be neces-
sary to obtain the proper volume of moisture.  

REQUIRED TOOLS:  

2.0  Aviation Snips  •  1/4" Flathead Screwdriver  •  #1 Phillips Screwdriver  •  
Adjustable Wrench  •  Pliers  •  Electric Drill with 7/64", 1/4" and 3/8" Drill Bits  •  
Hammer  •  Center Punch 

 

INSTALLATION INSTRUCTIONS 

Outside            

Temperature 

Recommended  

Setting 

Outside            

Temperature 

Recommended  

Setting 

-

20°F 

Low 

+10°F 

Med 

-

10°F 

Low 

+20°F 

High 

0°F 

Med 

Above +20°F 

High 

Table 1 

 

Capacities in G.P.H. at Various Water Pressures 

Nozzle Size  

40 P.S.I. 

60 P.S.I. 

80 P.S.I. 

100 P.S.I. 

125 P.S.I. 

.37 

.37 G.P.H. 

.45 G.P.H. 

.55 G.P.H. 

.60 G.P.H. 

.70 G.P.H. 

.50 

.50 G.P.H. 

.60 G.P.H. 

.70 G.P.H. 

.80 H.P.H. 

.85 G.P.H. 

.75 

.75 G.P.H. 

.89 G.P.H. 

1.10 G.P.H. 

1.20 G.P.H. 

1.40 G.P.H. 

1.00 

1.00 G.P.H. 

1.20 G.P.H. 

1.40 G.P.H. 

1.60 G.P.H. 

1.70 G.P.H. 

1.50 

1.50 G.P.H. 

1.80 G.P.H. 

2.10 G.P.H. 

2.40 G.P.H. 

2.70 G.P.H. 

2.00 

2.00 G.P.H. 

2.50 G.P.H. 

2.80 G.P.H. 

3.20 G.P.H. 

3.50 G.P.H. 

Table 2

 

 
 
 
 
 
 
 
 

101 Margaret Street, Marietta, OH 45750 

Phone: (800) 848-9786  •  Fax: (740) 373-9565 

Email: [email protected]  •  Web: www.skuttle.com 

GENERAL INFORMATION:  

3.0   

CAUTION: 

When  selecting  a  location  for  the  humidifier,  make  sure  the 

spray will not impinge or accumulate on any fan, limit controls, heating parts or 
A-coils. 

 

3.1    Select  a  location  where  the  air  will  push  the  spray  mist  away  from  the      
humidifier.  

3.2    Mount  the  humidifier  on  the  hot  air 
plenum only, with the nozzle pointing up in 
the direction of airflow (see Figure 1, left). 
On  narrow plenums, mount the humidifier 
on the narrow side.  
3.3  If there is not enough room on the hot 
air  plenum,  mount  the  humidifier  further 
downstream  on  the  warm  air  duct,  away 
from the heating and cooling coil.  
3.4    If  it  is  necessary  to  mount  the  spray 
nozzle further away from the humidifier (in 
order  to  move  the  nozzle  further  into  the 
air  stream  for  better  absorption),  remove 
the nozzle adapter and 45° fitting from the 
solenoid valve. Use the fittings supplied in 
the parts bag to relocate the nozzle using 
1/4"  copper  tubing  (not  supplied).  (See 
Figure  2,  below,  left.)    

CAUTION: 

Do not 

allow  copper  tubing  to  come  in  contact 
with  sharp  edges  or  surfaces  that  may 
cause wear on the tubing. 

 

3.5    Tape  the  template 
(provided)  on  the  warm  air 
plenum  in  the  location   
selected  for  the  humidifier. 

CAUTION: 

Make  sure  the 

template is level. 

 

3.6  Center punch and drill 
four  7/64"  mounting  holes, 
as  shown  on  the  template. 

DANGER: 

Make  sure  you 

are not cutting or drilling in-
to air conditioning or elec-  

                                                                                      trical accessories. 

 

3.7   Drill  a  3/8"  hole in  the 
center  portion  of  the  tem-
plate and cut a rectangular 
opening,  as  instructed  on 
the template.  
3.8    Install  the  drain  cup 
over  the  nozzle;  attach  it 
with  a  #6  x  3/8"  sheet 
metal  screw.  (See  Figure 
3, left.) 
3.9  Install 3/16" I.D. tubing 
on  the  copper  humidifier 
drain  and  run it  to  a  waste 
drain. (An occasional drip  
from the drain tube when  
the humidifier is operating  

                                                                                      is normal.) 
                                                                                      3.10  Attach the humidifier  
                                                                                      with four #8 sheet metal  
                                                                                      screws.  

 

PLUMBING THE HUMIDIFIER:  

4.0    Select  the  nearest  cold  water  pipe  and  install  the  saddle  connector  and 
needle valve, supplied with this unit. 

USE COPPER TUBING ONLY. 

 

The  needle  valve  is  a  self-piercing  valve  when  installed  on  copper  pipe.  
Follow the instructions supplied with the valve.  

Mount  the  valve  so  that  water  will  come  from  the  top  or  side.  This  will  re-
duce the chance of minerals clogging the valve.  

4.1  Follow these compression plumbing tips:  

Lightly  clean  the  tubing  ends  with  fine  sandpaper  before  making  connec-
tions.  

Make  sure  the  tubing  is  fully  inserted  into  the  fitting  before  tightening  the 
compression nut.  

4.3  

IMPORTANT: 

After attaching the saddle valve, thoroughly flush the supply 

tubing to clear the line. 

Otherwise, debris could block the water flow at the sole-

noid valve.  
4.4   

IMPORTANT: 

To  assist  you  with  cleaning,  note  the  proper  orientation  of 

parts for assembly and disassembly. (See Figure 4, on back.) 

 

 
 

Part No. 0756-163 
Rev. 7/03 

  BEGIN READING ON OPPOSITE PANEL 

 

Continued on back... 

Figure 1

 

Figure 2

 

Figure 3

 