1.0 Safety information
General safety notes
Carefully read the operating manual
before placing the unit in service
for the first time. It contains useful
tips and notes as well as hazard
warnings to prevent injury or
material damage. Failure to follow
the directions in this Manual can
endanger persons, the environment
and the equipment itself and will
void any claims for liability.
Keep this operating manual and
the refrigerant data sheet near to
the units.
•
Only qualified personnel may
set up and install the units and
components.
•
The set-up, connection and
operation of the units and its
components must be undertaken
in accordance with the usage and
operating conditions stipulated
in this manual and comply
with all applicable regional
regulations.
•
Mobile units must be set up
securely on suitable surfaces and
in an upright position. Stationary
units must be permanently
installed for operation.
•
Modification of the units and
components supplied by CLIMIA
is not permitted and can cause
malfunctions.
•
The units and components
should not be operated in areas
where there is an increased risk of
damage. Observe the minimum
clearances.
•
The electrical power supply
should be adapted to the
requirements of the units.
•
The operational safety of the
units and components is only
assured providing they are
used as intended and in a
fully assembled state. Safety
devices may not be modified or
bypassed.
•
Do not operate units or
components with obvious
defects or signs of damage.
•
All housing parts and unit
openings, e.g. air inlets and
outlets, must be free from foreign
objects, liquids and gases.
•
The units and components must
be kept at an adequate distance
from flammable, explosive,
combustible, abrasive and dirty
areas or atmospheres.
•
Contact with equipment parts or
components can lead to burns or
injury.
•
Installation, repair and
maintenance work may only
be carried out by authorised
specialists. Visual inspections and
cleaning can be performed by
the operator as long as the unit is
disconnected from the power.
•
Appropriate hazard prevention
measures must be taken to
prevent risks to people when
performing installation, repair,
maintenance or cleaning work on
the units.
•
The units and components
should not be exposed to any
mechanical load, extreme levels
of humidity or direct exposure to
sunlight.
Safety instructions for the
operator
•
The units and components must
not be exposed to any mechanical
load, extreme levels of humidity or
extreme temperatures. Operation
in rooms with possible ignition
sources (e.g. open flames, gas
heaters, electric heaters) is also
prohibited.
•
During operation of the unit, icing
of the heat exchangers may occur
occasionally. The units feature an
automatic defrosting function
if required. Never thaw the heat
exchangers independently!
•
The refrigerant R290 used in the
unit is highly flammable, invisible
and odourless. It is imperative
that the safety instructions in
the installation and operating
instructions are observed.
•
The unit may only be stored and
operated in rooms larger than 8
m².
•
Possible regional laws and
regulations must be observed.
•
Air intake and outlet areas must
be kept clear. Never cover the unit.
•
The unit must be stored in such a
way that mechanical damage can
be ruled out. The storage location
must be sufficiently large and well
ventilated.
Warning of inflammable
substances
CLIMIA
4
Summary of Contents for CMK 2600
Page 1: ...Edition 3 0 English CLIMIA Local room air conditioner CMK 2600 Operating manual ...
Page 2: ...CLIMIA ...
Page 14: ...15 0 Electrical wiring diagram Fig 12 Connection diagram CMK 2600 CLIMIA 14 ...
Page 19: ......
Page 20: ...Intakt GmbH Climia Klima und Wärmetechnik Niemeierstraße 13 D 32758 Detmold ...