21/28
2015/12 - Indice de révision : B - Code : 33491
The control panel is delivered with a wall mounting bracket.
1.
Remove the 2 screws from the mounting bracket.
2.
Mount the bracket on the wall in the desired position (out of the reach of children) using the 2 central
slots or the 4 peripheral slots (screws and bushings are not supplied).
3.
The cut out for the cable should face down
(to avoid streaming of condensates inside the control
panel).
4.
Unclip the rear casing of the control panel.
5.
Fix the rear casing of the control panel to the bracket using the 2 screws previously removed from
the mounting bracket.
6.
Clip the control panel onto its rear face.
Electrical wiring
The power cable is comprised of three strands (live = brown ; neutral =
blue ; earth = green and yellow), it is 1.5 m long.
To extend the power cable, use a cable with strands of the same cross section
if the total length of the cable will not exceed 10 m. If the cable in longer than
10 m, use an extension cable with strands that have a wider cross section.
Solder the wires together, use heat shrink tubing to insulate the soldered
connections.
The power cable must be connected to a thermal
magnetic protection device or a fuse fuse,
rated fro the machine’s power consumption.
We strongly recommend that the machine’s power
line be protected by a 30 mA RCD.
Even with an extension, the control cable may not be longer than 50 meters. To extend the cable, use
cable with the same cross sections and connect the wires as described previously.
Type
DH 60
DH 90
DH 120
Residual current
device
Nominal current ( Amps)
20
30
40
Trip current mA
30
30
30
d curve thermal magnetic circuit breaker -
Nominal trip current in (A)
DH without
heater
7 (8 if not
adjustable)
11 (16 if not
adjustable)
12 (16 if not
adjustable)
DH with
heater
16
25
26 (32 if not
adjustable)
Power cable (mm2)
3 x 2,5
3 × 4
3 × 4
Remote installed control pad cable (mm2)
3 × 0.5
3 × 0.5
3 × 0.5
Support de fixation
Panneau arrière
commande