ECO series ModBus register map
Parameter file
settings (4x)
Unit/Value
Description
35201
Temperature setpoint
min limit
0,1 °C
E.g. 200 = 20,0°C.
NOTE ! Must be dividable by 5 (0,5°C)
35202
Temperature setpoint
max limit
0,1 °C
E.g. 200 = 20,0°C.
NOTE ! Must be dividable by 5 (0,5°C)
35203
Temperature setpoint
normal
0,1 °C
NOTE! Use 4x4 instead
35204
Temperature setpoint
away
0,1 °C
E.g. 200 = 20,0°C.
NOTE ! Must be dividable by 5 (0,5°C)
35205
Not used
35206
Week timer master
off/on
0 = Off, 1 = On
This is same as 4x2000. Does not matter which one you use
35225
Thermostat adaptivity
1 = Off, 1 = On
35226
Temp calibration
0,1 °C
E.g. 10 = +1,0°C
59001
Active week program
setpoint
0,1 °C
Read only
Input
registers (3x)
Unit/Value
Description
5
HW revision
6
SW version major
7
SW version minor
8
Room temperature
0,1 °C
9
Not used
10
Not used
11
Application state
12
Application status
13
Not used
14
Temperature setpoint
0,1 °C
15
Last user activity
(Touch display)
sec
16
Not used
17
Start unit
18
Heating load
%