climecon.fi
© Climecon
10
ECO series ModBus register map
Holding
registers (4x)
Unit/Value
Description
2014
Not used
Must be 1
2015
Week program 3
- Comfort start time
Minutes after midnight. 0 = 0:00,
NOTE ! Must be dividable by 15
2016
Week program 3
- Comfort end time
Minutes after midnight. 0 = 0:00,
NOTE ! Must be dividable by 15
2017
Week program 3
- Comfort temperature
0,1 °C
E.g. 200 = 20,0°C.
NOTE ! Must be dividable by 5 (0,5°C)
2018
Week program 3
- Economy temperature
0,1 °C
E.g. 200 = 20,0°C.
NOTE ! Must be dividable by 5 (0,5°C)
2019
Week program 4
off/on
bit 0 = Monday off/on, bit 1=Tuesday off/on, bit 2=Wednesday off/
on, bit 3=Thursday off/on, bit 4=Friday off/on , bit 5=Saturday off/on,
bit 6=Sunday off/on, bit 7=program1 off/on
2020
Not used
Must be 1
2021
Week program 4
- Comfort start time
Minutes after midnight. 0 = 0:00,
NOTE ! Must be dividable by 15
2022
Week program 4
- Comfort end time
Minutes after midnight. 0 = 0:00,
NOTE ! Must be dividable by 15
2023
Week program 4
- Comfort temperature
0,1 °C
E.g. 200 = 20,0°C.
NOTE ! Must be dividable by 5 (0,5°C)
2024
Week program 4
- Economy temperature
0,1 °C
E.g. 200 = 20,0°C.
NOTE ! Must be dividable by 5 (0,5°C)
2025
Week program5 off/on
bit 0 = Monday off/on, bit 1=Tuesday off/on, bit 2=Wednesday off/
on, bit 3=Thursday off/on, bit 4=Friday off/on , bit 5=Saturday off/on,
bit 6=Sunday off/on, bit 7=program1 off/on
2026
Not used
Must be 1
2027
Week program 5
- Comfort start time
Minutes after midnight. 0 = 0:00,
NOTE ! Must be dividable by 15
2028
Week program 5
- Comfort end time
Minutes after midnight. 0 = 0:00,
NOTE ! Must be dividable by 15
2029
Week program 5
- Comfort temperature
0,1 °C
E.g. 200 = 20,0°C.
NOTE ! Must be dividable by 5 (0,5°C)
2030
Week program 5
- Economy temperature
0,1 °C
E.g. 200 = 20,0°C.
NOTE ! Must be dividable by 5 (0,5°C)
35001
Parameter system
version
Read only
35002
Not used (NULL)
Read only
35003
Not used (NULL)
Read only
35004
Parameter file revision
Read only
35005
Parameter request
revision
Read only