The air flow sensor is delivered together with the CCM control unit.
1.
Find a suitable place for the air flow sensor in the exhaust air duct. It is recommended to install
it in a straight section of the duct (less turbulence), preferably not on the bottom of the duct.
2.
Drill a Ø24mm hole into the duct.
3.
Fix the air flow sensor to a mounting plate. Adjust the installation depth according to the dia-
meter of the exhaust air duct. It is recommended to install it in the centre of the duct (Figure 1).
4.
Make sure that the air flow sensor is installed according to the air flow direction. See the arrow
at the bottom of the sensor (Figure 2).
5.
Drill pilot holes for the fixing screws of the mounting plate.
6.
Fix the air flow sensor to the duct.
Figure 1. Installation depth of air flow sensor
3.2 Installation of the air flow sensor
min. 32 mm
approx. 120 mm
Figure 2. Installation direction of the air flow sensor
Installation direction of the air flow sensor