10

i-LIFE SLIM  

EN 05/2013

C

A

 (Ø14mm)

B

CONDENSATE DRAIN

I A

The condensate drain line must be suitably sized (pipe with
a minimum inside diameter of 16 mm) and the pipe laid out
as to ensure a minimum slope of 1% along the entire line. 
For vertical installation, the drain line is connected directly to
the  drain  pan,  located  at  the  bottom  of  the  side  frame,
underneath the water connections.
For horizontal installation, the drain line is connected to the
drain pipe already fitted on the unit.
For  horizontal  installation  of  DLMO  versions,  the  horizontal
condensate collection pan kits are available as accessories.
-  If possible, discharge the condensate directly into a gutter

or a storm water drain.

- If draining into the sewers, a drain trap should be fitted to

prevent bad odours from drifting back into the rooms. 
The bend in the drain trap must be lower than the conden-
sate collection pan.

-  If  discharging  the  condensate  into  a  container,  this  must

be open and the drain pipe must not be immersed in the

water,  so  as  to  avoid  surface  tension  and  backpressure
that would prevent correct drainage.

-  If needing to overcome a raised section that wold prevent

condensate drainage, a pump must be installed:

-  for  vertical  installation,  fit  the  pump  underneath  the  side

drain pan;

- for horizontal installation, the position of the pump should

be determined according to specific needs.

These pumps are widely available on the market.
In any case, following installation check correct condensate
drainage  by  pouring  very  slowly  (around  1/2  l  of  water  in
around 5-10 minutes) into the collection pan.

drain fitting

B

drain pipe

C

drip guard

Assembling  the  condensate  drain  pipe  on  vertical  ver-
sions

Connect a drain pipe to the condensate collection pan drain
fitting and secure it in place.

Make sure that the drip guard is installed correctly.

WATER CONNECTIONS 

I A

The choice and sizing of the water lines is the responsibility
of  the  designer,  who  must  apply  best  working  practice  and
comply  with  the  legislation  in  force,  also  considering  that
undersized lines will lead to poor performance.

To make the connections:
-  position the water lines 
-  tighten  the  connections  using  two  spanners  in  opposite

directions

-  check for any leaks
-  cover the connections with insulating material

The water lines and the joints must be thermally insulated.

Make sure the pipes are completely insulated.

Avoid over-tightening so as to not damage the insulation.

To  ensure  water  tightness  of  threaded  connections,  use
plumber’s  hemp  and  green  paste;  Teflon  tape  is  recom-
mended when antifreeze is added to the water circuit.

Dimensions 

102

202

302

402

502

Pipe diameter

mm

12

14

16

18

20

Summary of Contents for i-LIFE SLIM 102

Page 1: ...Fan coil with casing or for built in installation with tangential fan and inverter controlled brushless motor EN i LIFE SLIM 102 502 INSTALLATION USER MAINTENANCE MANUAL...

Page 2: ...llation procedure 6 Minimum installation clearance 6 Dismantling assembling the casing 7 Vertical installation 7 Horizontal installation 8 Fixing the front intake grill 8 Front grill safety support as...

Page 3: ...appliance These appliances have been designed for cooling and heating rooms and must be used in applications compat ible with their performance characteristics Incorrect installation adjustment and m...

Page 4: ...SPECIFICATIONS i LIFE SLIM 102 202 302 402 502 Coil water content l 0 47 0 8 1 13 1 46 1 8 Maximum operating pressure bar 10 10 10 10 10 Maximum water inlet temperature C 80 80 80 80 80 Minimum water...

Page 5: ...a macchina XYZ XYZ Codice di identificazione 00123 01 2001 MODELLO 10 20 30 40 50 60 70 Potenza frigorifera kW 12 15 17 34 56 77 84 Potenza termica KW 23 33 43 53 63 65 90 Portata aria mc 330 550 670...

Page 6: ...ion at the intake and outlet the wall where the unit is installed should be an outside perimeter wall so as to be able to drain the conden sate outside in the event of ceiling installation DLMO or DLI...

Page 7: ...ing the mouldings Use the paper template and trace the position of the two fastening brackets on the wall Drill the holes with a suitable drill bit and insert the anchors 2 for each bracket fasten the...

Page 8: ...re available as accessories DLRV versions must not be installed horizontally Carefully check the slope of the drain pipe If the drain line is not sloping downwards water may leak from the line A A B B...

Page 9: ...provided in the bag supplied together with the instruction booklet and the accessories These supports are designed to stop the grill from falling Separate the two clamps open the front grill and comp...

Page 10: ...it the pump underneath the side drain pan for horizontal installation the position of the pump should be determined according to specific needs These pumps are widely available on the market In any ca...

Page 11: ...nd return pipes all the way to the unit so as to prevent condensate from dripping out side of the collection pan insulate the entire condensate pan drain pipe A A FILLING THE SYSTEM I A A Coil vent Wh...

Page 12: ...the Technical Service and using orig inal spare parts when required CLEANING THE OUTSIDE OF THE UNIT I A Before any cleaning and maintenance work disconnect the unit from the mains power supply switch...

Page 13: ...tom edge is correctly fitted in place Never use the appliance without the mesh filter The appliance is fitted with a safety switch that prevents the fan from operating if the panel is not fitted or is...

Page 14: ...d make sure the fan can spin freely The microswitch that stops the fan when opening the filter grill does not close correctly Make sure that when closing the grill the microswitch contact is activated...

Page 15: ...COD C01002328A_02...

Reviews: