![CLIMAVENETA Accurate AD Installation - User - Maintenance Manual Download Page 52](http://html.mh-extra.com/html/climaveneta/accurate-ad/accurate-ad_installation-user-maintenance-manual_2624838052.webp)
CALIBRATING THE CONTROL AND SAFETY DEVICES
52
EN
ACCURATE AX - AW - AD - AT - AF
After starting the air-conditioner, make the following adjustments:
- Room temperature (cooling and heating set point).
- Relative humidity (set point for humidification and dehumidifi-
cation);
- Dirty filter differential pressure switch: see the paragraph on
"CALIBRATING THE DIRTY FILTER SENSOR".
The calibration values of the control and safety devices must not
be altered.
Symbol
Description
Models
Activation
Differential
Reset
F1
High pressure switch
5
37,4 bar (opening)
-
Manual reset
7
38,7 bar (opening)
10
15
18
20
30
40
26
40,5 bar (opening)
29
39
50
55
60
70
80
90
F2
Low pressure switch
All
3,0 bar (opening)
0,9 bar
3,9 bar (automatic)
TH1
Safety thermostat (versions T and H)
All
320 °C (opening)
-
Manual reset
VS
Safety valve
05
41,5 bar
-
-
07
43 bar
10
15
18
20
30
40
26
45 bar
29
39
50
55
60
70
80
90