ELECTRICAL CONNECTION OF THE OUTDOOR AIR-COOLED
CONDENSER BRE AND/OR THE OUTDOOR DRY COOLER BDC
48
EN
ACCURATE AX - AW - AD - AT - AF
It must be stressed that both the standard air-cooled condensers
and dry coolers supplied by the manufacturer are not fitted as
standard with the condenser fan speed controller, and are only
electrically connected to the disconnect switch for local mainte-
nance operations (for further details, see the manual on the out-
door air-cooled condensers and dry coolers).
Therefore, both of these outdoor units can be powered directly
via the disconnect switch with primary voltage, however this
means their operation is not controlled.
If the indoor units used are the ACCURATE in MODULATING
version, complete with condenser fan speed controller, the outdoor
air-cooled condenser and/or dry cooler can be connected/powered
directly from the panel on the indoor unit (the connection cable is
not supplied by the manufacturer).
The instructions on the connection and the size of the power
cables are provided by the manufacturer on the wiring diagram
on the indoor unit. For both single and dual circuit models, just
one connection/power cable is required between the indoor and
outdoor unit. The voltage delivered will be modulated by the con-
denser control unit installed on the indoor unit, based on the cur-
rent requirements of the system.
This ensures optimum operating conditions.
The condenser control unit is also featured as standard on the
versions of the indoor units for low outside temperatures (-
45°C).
For the parameter setting of control condensation refer
to the manual of the controller EV.
Values for individual component
FLI = Maximum power consumption
FLA = Max current
Vers.
Unit power supply
Humidifier modulating
Frame
Mod.
V/ph/Hz
V/ph/Hz
Qty.
FLI (kW) FLA (A)
kg/h
1
05
/
/
/
/
/
/
1
07
380/3/60
380/3/60
1
2,11
3,4
2,8
1
10
380/3/60
380/3/60
1
2,11
3,4
2,8
2
15
380/3/60
380/3/60
1
3,55
5,7
4,7
2
18
380/3/60
380/3/60
1
3,55
5,7
4,7
3
20
380/3/60
380/3/60
1
3,55
5,7
4,7
3
26
380/3/60
380/3/60
1
3,55
5,7
4,7
3
29
380/3/60
380/3/60
1
3,55
5,7
4,7
4
39
380/3/60
380/3/60
1
3,55
5,7
4,7
4
30
380/3/60
380/3/60
1
3,55
5,7
4,7
4
40
380/3/60
380/3/60
1
3,55
5,7
4,7
4
50
380/3/60
380/3/60
1
3,55
5,7
4,7
5
55
380/3/60
380/3/60
1
5,73
9,1
7,6
5
60
380/3/60
380/3/60
1
5,73
9,1
7,6
5
70
380/3/60
380/3/60
1
5,73
9,1
7,6
6
80
380/3/60
380/3/60
1
5,73
9,1
7,6
6
90
380/3/60
380/3/60
1
5,73
9,1
7,6
Vers.
Unit power supply
Humidifier modulating
Frame
Mod.
V/ph/Hz
V/ph/Hz
Qty.
FLI (kW) FLA (A)
kg/h
1
05
/
/
/
/
/
/
1
07
230/3/60
230/3/60
1
2,25
5,6
3
1
10
230/3/60
230/3/60
1
2,25
5,6
3
2
15
230/3/60
230/3/60
1
3,75
9,4
5
2
18
230/3/60
230/3/60
1
3,75
9,4
5
3
20
230/3/60
230/3/60
1
3,75
9,4
5
3
26
230/3/60
230/3/60
1
3,75
9,4
5
3
29
230/3/60
230/3/60
1
3,75
9,4
5
4
39
230/3/60
230/3/60
1
3,75
9,4
5
4
30
230/3/60
230/3/60
1
3,75
9,4
5
4
40
230/3/60
230/3/60
1
3,75
9,4
5
4
50
230/3/60
230/3/60
1
3,75
9,4
5
5
55
230/3/60
230/3/60
1
6
16,7
8
5
60
230/3/60
230/3/60
1
6
16,7
8
5
70
230/3/60
230/3/60
1
6
16,7
8
6
80
230/3/60
230/3/60
1
6
16,7
8
6
90
230/3/60
230/3/60
1
6
16,7
8