POWER CONSUMPTION OF INDIVIDUAL COMPONENTS (HUMIDIFIER)
Values for individual component
FLI = Maximum power consumption
FLA = Max current
Vers.
Unit power supply
STD electric heaters
HIGH POWER electric heaters
Frame
Mod.
V/ph/Hz
V/ph/Hz
Qty.
FLI (kW)
FLA (A)
V/ph/Hz
Qty.
FLI (kW)
FLA (A)
1
05
/
/
/
/
/
/
/
/
/
1
07
230/3/60
230/3/60
2
4,2
10,6
230/3/60
3
6
15,1
1
10
230/3/60
230/3/60
2
4,2
10,6
230/3/60
3
6
15,1
2
15
230/3/60
230/3/60
2
8,1
20,4
230/3/60
3
12
30,2
2
18
230/3/60
230/3/60
2
8,1
20,4
230/3/60
3
12
30,2
3
20
230/3/60
230/3/60
3
9
22,6
230/3/60
5
15
37,7
3
26
230/3/60
230/3/60
3
9
22,6
230/3/60
5
15
37,7
3
29
230/3/60
230/3/60
3
9
22,6
230/3/60
5
15
37,7
4
39
230/3/60
230/3/60
5
15
37,7
230/3/60
6
18
45,2
4
30
230/3/60
230/3/60
5
15
37,7
230/3/60
6
18
45,2
4
40
230/3/60
230/3/60
5
15
37,7
230/3/60
6
18
45,2
4
50
230/3/60
230/3/60
5
15
37,7
230/3/60
6
18
45,2
5
55
230/3/60
230/3/60
6
18
45,2
230/3/60
9
27
69
5
60
230/3/60
230/3/60
6
18
45,2
230/3/60
9
27
69
5
70
230/3/60
230/3/60
6
18
45,2
230/3/60
9
27
69
6
80
230/3/60
230/3/60
6
18
45,2
230/3/60
9
27
69
6
90
230/3/60
230/3/60
6
18
45,2
230/3/60
9
27
69
Vers.
Unit power supply
Humidifier modulating
Frame
Mod.
V/ph/Hz
V/ph/Hz
Qty.
FLI (kW) FLA (A)
kg/h
1
05
230/1/50
230/1/50
1
2,25
9,8
3
1
07
230/1/50
230/1/50
1
2,25
9,8
3
1
10
230/1/50
230/1/50
1
2,25
9,8
3
2
07
400/3N/50
400/3/50
1
2,25
3,2
3
2
10
400/3N/50
400/3/50
1
2,25
3,2
3
2
15
400/3N/50
400/3/50
1
3,75
5,5
5
2
18
400/3N/50
400/3/50
1
3,75
5,5
5
3
20
400/3N/50
400/3/50
1
3,75
5,5
5
3
26
400/3N/50
400/3/50
1
3,75
5,5
5
3
29
400/3N/50
400/3/50
1
3,75
5,5
5
4
39
400/3N/50
400/3/50
1
3,75
5,5
5
4
30
400/3N/50
400/3/50
1
3,75
5,5
5
4
40
400/3N/50
400/3/50
1
3,75
5,5
5
4
50
400/3N/50
400/3/50
1
3,75
5,5
5
5
55
400/3N/50
400/3/50
1
6
8,7
8
5
60
400/3N/50
400/3/50
1
6
8,7
8
5
70
400/3N/50
400/3/50
1
6
8,7
8
6
80
400/3N/50
400/3/50
1
6
8,7
8
6
90
400/3N/50
400/3/50
1
6
8,7
8
Vers.
Unit power supply
Humidifier modulating
Frame
Mod.
V/ph/Hz
V/ph/Hz
Qty.
FLI (kW) FLA (A)
kg/h
1
05
/
/
/
/
/
/
1
07
460/3/60
460/3/60
1
2,25
2,8
3
1
10
460/3/60
460/3/60
1
2,25
2,8
3
2
15
460/3/60
460/3/60
1
3,75
4,7
5
2
18
460/3/60
460/3/60
1
3,75
4,7
5
3
20
460/3/60
460/3/60
1
3,75
4,7
5
3
26
460/3/60
460/3/60
1
3,75
4,7
5
3
29
460/3/60
460/3/60
1
3,75
4,7
5
4
39
460/3/60
460/3/60
1
3,75
4,7
5
4
30
460/3/60
460/3/60
1
3,75
4,7
5
4
40
460/3/60
460/3/60
1
3,75
4,7
5
4
50
460/3/60
460/3/60
1
3,75
4,7
5
5
55
460/3/60
460/3/60
1
6
7,5
8
5
60
460/3/60
460/3/60
1
6
7,5
8
5
70
460/3/60
460/3/60
1
6
7,5
8
6
80
460/3/60
460/3/60
1
6
7,5
8
6
90
460/3/60
460/3/60
1
6
7,5
8