68
G e o t h e r m a l H e a t i n g a n d Co o l i n g
Trilogy
®
Q-Mode
®
(QE) Series IOM - 60Hz HFC-410A
R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1
Table 16: Troubleshooting
Code
Fault
Mode
Possible Cause
Solution
2
High Discharge Pressure
CL
Reduced or no water flow
Check loop pump operation
CL
Reduced or no water flow
Check water flow and adjust to proper flow rate
CL, HW
Water temp out of range
Bring water temp within design parameters
HW
Reduced or no water flow
Check HW pump operation
HW
Reduced or no water flow
Check water flow and adjust to proper flow rate
HT
Reduced or no air flow
Check for dirty air filter - clean or replace
HT
Reduced or no air flow
Check fan motor operation and air flow restrictions
HT
Reduced or no air flow
Dirty air coil
HT
Reduced or no air flow
External static is too high - correct duct work
HT
Air temp out of range
Bring air temp within design parameters
ALL
Overcharged
Check superheat and subcooling vs. manual mode operating condition
table
ALL
Faulty discharge transducer
Check transducer
3
Low Suction Pressure
ALL
Insufficient charge
Check for refrigerant leaks
HT, HW
Incorrect loop configuration
Check freeze protection trip point setting
HT, HW
Reduced or no water flow
Check loop pump operation
HT, HW
Reduced or no water flow
Check water flow and adjust to proper flow rate
CL, HW Reduced or no air flow
Check for dirty air filter - clean or replace
CL, HW Reduced or no air flow
Check fan motor operation and air flow restrictions
CL, HW Reduced or no air flow
Dirty air coil
CL, HW Reduced or no air flow
External static is too high - correct duct work
HT, HW
Improperly functioning EEV1
Check coil windings with ohmmeter. WHITE/RED, GREEN/RED,
YELLOW/VIOLET, and BLUE/VIOLET should each read between 36
and 44 ohms.
HT, HW
Improperly functioning EEV1
Check output signal from EXM.
CL, HW Improperly functioning EEV2
Check coil windings with ohmmeter. WHITE/RED, GREEN/RED,
YELLOW/VIOLET, and BLUE/VIOLET should each read between 36
and 44 ohms.
CL, HW Improperly functioning EEV2
Check output signal from EXM.
HT, HW Water temp out of range
Bring water temp within design parameters
CL, HW
Air temp out of range
Bring air temp within design parameters
ALL
Faulty suction transducer
Check transducer
ALL
Faulty check valve
Check different operational modes to isolate valve
ALL
Restriction after the EEV
Check for temperature drop at various sections along refrigerant
circuit. i.e., across filter-dryer, etc.
6
Condensate Overflow
ALL
Blocked Drain
Check for blockage and clean drain.
ALL
Improper Trap
Check trap dimensions and location ahead of vent
CL, HW Poor drainage
Check for piping slope away from unit
CL, HW Poor drainage
Check slope of unit towards outlet
CL, HW Poor drainage
Poor venting - check vent location
CL, HW Moisture on sensor
Check for moisture shorting to air coil
ALL
Plugged air filter
Clean or replace air filter
ALL
Restricted return air flow
Find and eliminate restriction - increaes return duct and/or grille size
7
Over / Under Voltage
ALL
Under voltage
Check power supply and 24Vac before and during operation
ALL
Under voltage
Check power supply wires
ALL
Under voltage
Check 24Vac transformer tap for correct power supply voltage
ALL
Over voltage
Check power supply and 24Vac before and during operation
ALL
Over voltage
Check 24Vac transformer tap for correct power supply voltage