![ClimateMaster Trilogy Q-Mode (QE) Series Manual Download Page 36](http://html1.mh-extra.com/html/climatemaster/trilogy-q-mode-qe-series/trilogy-q-mode-qe-series_manual_2624790036.webp)
36
G e o t h e r m a l H e a t i n g a n d Co o l i n g
Trilogy
®
Q-Mode
®
(QE) Series IOM - 60Hz HFC-410A
R e v i s e d : D e c e m b e r 2 2 , 2 0 2 1
Trilogy
Model
Max ESP
(in wg)
Fan
Motor
(hp)
Range
Capacity
Cooling
Mode
Dehum
Heating
Mode
Fan Only
Mode
Aux
Emerg
Mode
0930
0.4
5
at
1125; 0.75
at 1000
1/2
Default
9,000
300
275
300
350
850
12,000
425
375
425
15,000
500
450
500
18,000
600
525
600
21,000
700
600
700
24,000
775
675
775
27,000
875
750
875
30,000
950
800
950
Minimum
9,000
225
225
200
225
700
12,000
275
275
225
15,000
325
325
300
18,000
425
425
375
21,000
500
500
450
24,000
575
575
525
27,000
650
650
600
30,000
750
750
700
Maximum
9,000
375
375
375
1125
1125
12,000
525
525
525
15,000
650
650
650
18,000
750
750
750
21,000
850
850
850
24,000
975
975
975
27,000
1075
1075
1075
30,000
1125
1125
1125
1860
0.45 at
2250; 0.75
at 2000
1
Default
18,000
600
525
600
700
1500
24,000
775
675
775
30,000
975
825
975
36,000
1150
1000
1150
42,000
1325
1150
1325
48,000
1525
1325
1525
54,000
1700
1475
1700
60,000
1875
1625
1875
Minimum
18,000
425
425
375
425
1350
24,000
575
575
525
30,000
725
725
675
36,000
875
875
800
42,000
1025
1025
950
48,000
1200
1200
1075
54,000
1350
1350
1225
60,000
1500
1500
1375
Maximum
18,000
750
750
750
2250
2250
24,000
975
975
975
30,000
1175
1175
1175
36,000
1400
1400
1400
42,000
1600
1600
1600
48,000
1825
1825
1825
54,000
2025
2025
2025
60,000
2250
2250
2250
Airflow is controlled within 5% up to the Max ESP shown with wet coil
ECM Blower Performance Data