![ClimateMaster trilogy 45 q-mode series User Manual Download Page 52](http://html1.mh-extra.com/html/climatemaster/trilogy-45-q-mode-series/trilogy-45-q-mode-series_user-manual_2624756052.webp)
QE
52
Trilogy
®
45 Q-Mode
®
(QE) Series
ClimateMaster: Declare your personal energy independence.
Auxiliary Heat Electrical Data
Auxiliary Heat Ratings
Auxiliary Electric Heat
Auxiliary Electric
Heat Model
Supply
Circuit
Heater Amps
Minimum Circuit Amps
Maximum Fuse
240V
208V
240V
208V
240V
208V
AGM4A
Single
15.8
14.0
19.8
17.1
20
20
AGM5A
Single
20.0
17.3
25.0
21.6
25
25
AGM8A
Single
31.7
27.5
39.6
34.4
40
35
AGM10A
Single
40.0
34.7
50.0
43.4
50
45
AGL10A
Single
40.0
34.7
50.0
43.4
50
45
AGM12A
Single
47.5
41.2
59.4
51.5
60
60
Dual-L1/L2
31.7
27.5
39.6
34.4
40
35
Dual - L3/L4
15.8
13.7
19.8
17.1
20
20
AGL15A
Single
60.0
52.0
75.0
65.0
80
70
Dual - L1/L2
40.0
34.7
50.0
43.4
50
45
Dual - L3/L4
20.0
17.3
25.0
21.6
25
25
AGL20A
Single
80.0
69.3
100.0
86.6
100
90
Dual - L1/L2
40.0
34.7
50.0
43.4
50
45
Dual - L3/L4
40.0
34.7
50.0
43.4
50
45
All heaters rated single phase 208/240V 60Hz
All Fuses UL Class K general purpose
All models 12kW or larger feature internal circuit breakers
Auxiliary
Electric
Heat
Model
QE Models
kW Rating
Btuh Rating
Minimum
CFM
Required
0930
1860
240V
208V
240V
208V
AGM4A
3.8
2.9
13000
9900
500
AGM5A
4.8
3.6
16300 12300
500
AGM8A
7.6
5.7
25900 19400
650
AGM10A
9.6
7.2
32700 24600
650
AGL4A
3.8
2.9
13000
9900
500
AGL10A
9.6
7.2
32700 24600
1300
AGL15A
14.4
10.8
49100 36900
1350
AGL20A
19.2
14.4
65500 49200
1350
Black area denotes compatibility
Note: Horizontal units rated for zero clearance unit and 1” clearance for the fi rst three feet of duct,
Vertical units rated for zero clearance for both unit and duct.