ClimateMaster Tranquility THW Series Installation Operation & Maintenance Download Page 18

C L I M A T E M A S T E R   W A T E R - S O U R C E   H E A T   P U M P S

18

C l i m a t e M a s t e r   W a t e r- S o u r c e   H e a t   P u m p s

Tr a n q u i l i t y

®

  W a t e r- t o - W a t e r   T H W   S e r i e s

R e v i s e d :   0 2   J a n u a r y,   2 0 1 3

10

15

20

25

30

35

40

45

50

55

30

25

20

15

10

5

0

-5

-10 -15 -20 -25 -30

Outdoor Temperature, °C

Buffer Tank Temperature, °C

Maximum

Buffer Tank

Temperature

52°C

20°C

Minimum

Buffer Tank

Temperature

Building

Balance

Point

Temperature

Outdoor

Design

Temperature

Figure 11:  Example Outdoor Temperature Reset

Table 6:  Buffer Tank Interface Inputs

Setting Description

Range

Default

Buffer Tank Set Point

21-60°C

38°C

Buffer Tank Deadband

2-11°C

3°C

Outdoor Design Temp

-40-10°C

-18°C

Maximum Design 

Water Temp

27-60°C

54°C

Minimum Design 

Water Temp

21-49°C

21°C

Building Balance 

Point Temp

10-21°C

16°C

The maximum design water temperature must be equal the buffer 
tank setpoint. The buffer tank setpoint will override the maximum 
design temperature if they are entered with different values. 

Electrical - Controls

There are four outdoor reset variables used for 
reducing the buffer tank setpoint.  The outdoor 
design temperature (ODT) is the OAT above which 
setpoint reduction begins.  The valid range for ODT 
is -40°C to 10°C, with a default value of -18°C.  The 
maximum design buffer tank temperature (MaxBT) 
is the maximum desired buffer tank setpoint at the 
outdoor design temperature.  The valid range for 
MaxBT is 27-60°C, with a default value of 54°C.  The 
building balance point temperature (the temperature 
at which heating is no longer needed) is the OAT at 
which maximum setpoint (MaxBT) reduction will occur.  
The valid range for building balance point is 10-21°C, 
with a default value of 16°C.  The minimum design 
water temperature is the minimum desired buffer tank 

setpoint at the building balance point temperature.  
The valid range for minimum buffer tank temperature is 
21-49°C, with a default value of 21°C.  If an OAT sensor 
is not detected (or if a thermistor error has occurred), 
the buffer tank setpoint will not be reduced based on 
the OAT value (i.e. the controller will use the buffer tank 
setpoint as described in the previous paragraph). 

Figure 11 shows an example outdoor temperature 
reset curve for a climate that has an outdoor design 
temperature of -20°C.  At design temperature, the 
radiant fl oor system needs 52°C water.  However, when 
the outdoor temperature is 20°C, the home needs no 
heating (building balance point).  In between -20°C 
and 20°C, the water temperature in the buffer tank is 
adjusted accordingly.  For homes that are well insulated 
and tightly sealed, the building balance point may be 
13°C or lower, so the slope of the line changes based 
upon settings at the user interface.  The radiant fl oor 
design temperature will also change the slope of the 
line.  If tighter pipe spacing is used, for example, the 
water temperature at the outdoor design temperature 
may only be 38°C.  Again, as the settings are changed 
at the user interface, the slope of the line will change.  
As mentioned earlier, the lower the heating water 
temperature at design conditions, the higher the 
effi ciency (COP) of the heat pump.  The combination of 
a lower design temperature and outdoor temperature 
reset can result in a signifi cant impact on operating 
costs.

Summary of Contents for Tranquility THW Series

Page 1: ...Load Plumbing Installation 7 Ground Water Heat Pump Application 9 Water Quality Standards 10 Ground Loop Heat Pump Application 11 Electrical Line Voltage 13 Electrical Low Voltage 15 Electrical Contro...

Page 2: ...CLIMATEMAS TE R WATE R S OURCE H E A T P UMP S 2 ClimateMaster Water Source Heat Pumps Tranqu ility Water to Water THW Ser ies Revis ed 02 J an uary 2013 This Page Intentionally Left Blank...

Page 3: ...requirements WARNING All refrigerant discharged from this unit must be recovered WITHOUT EXCEPTION Technicians must follow industry accepted guidelines and all local state and federal statutes for th...

Page 4: ...an up Examine all pipes fittings and valves before installing any of the system components Remove any dirt or trash found in or on these components Pre Installation Installation Operation and Maintena...

Page 5: ...utdoor Source Water Connection Size FPT in 1 1 1 Domestic Hot Water Connection Size FPT in 1 1 1 Weight Operating kg 207 207 234 Weight Packaged kg 214 214 241 Dual isolation compressor mounting Balan...

Page 6: ...should take care to comply with all building codes and allow adequate clearance for future field service Model Overall Cabinet Water Connections Electric Access Plugs 1 2 3 4 5 6 A Depth B Width C He...

Page 7: ...r service personnel to perform typical maintenance or repairs The installation of water source heat pump units and all associated components parts and accessories which make up the installation shall...

Page 8: ...U 7 XQLWV RQ ORDG DQG VRXUFH FRQQHFWLRQV 2WKHU FRPSRQHQWV DGGLWLRQDO EDOO YDOYHV XQLRQV HWF PD EH UHTXLUHG IRU HDVH RI VHUYLFH 7KLV GUDZLQJ VKRZV RQO PLQLPXP UHTXLUHPHQWV RXU VSHFLILF LQVWDOODWLRQ ZLO...

Page 9: ...codes i e recharge well storm sewer drain field adjacent stream or pond etc Most local codes forbid the use of sanitary sewer for disposal Consult your local building and zoning department to assure c...

Page 10: ...tered for maximum 841 micron 0 84 mm 20 mesh size Any particulate that is not removed can potentially clog components Notes Rev 3 22 2012 15 Application not recommended 1R GHVLJQ 0D LPXP ORVHG 5HFLUFX...

Page 11: ...rom a garden hose through flush cart before using flush cart pump to ensure an even fill Once full do not allow the water level in the flush cart tank to drop below the pump inlet line or air can be p...

Page 12: ...your area Freeze protection should be maintained to 9 4 C below the lowest expected entering loop temperature All alcohols should be premixed and pumped from a reservoir outside of the building when...

Page 13: ...al Line Voltage WARNING To avoid possible injury or death due to electrical shock open the power supply disconnect switch and secure it in an open position during installation Model Voltage Code Volta...

Page 14: ...A T P UMP S 14 ClimateMaster Water Source Heat Pumps Tranqu ility Water to Water THW Ser ies Revis ed 02 J an uary 2013 Electrical Line Voltage Field Low Voltage Wiring Field Line Voltage Wiring Figu...

Page 15: ...iagram for details Low Water Temperature Cutout FP1 The CXM DXM control allows the field selection of source fluid low temperature cutout points The factory setting of FP1 is set for water 1 1 C In co...

Page 16: ...boards Remove the yellow wire from the CXM board and connect it to terminal 2 on the valve Add a new wire from terminal 3 to the Y terminal at the CXM board and a jumper wire from terminal 1 to termi...

Page 17: ...ble controller as outlined above is the ability to integrate complex decision making tasks with the standard heat pump CXM controls and communicate with a user interface Below is a list of standard fe...

Page 18: ...OAT at which maximum setpoint MaxBT reduction will occur The valid range for building balance point is 10 21 C with a default value of 16 C The minimum design water temperature is the minimum desired...

Page 19: ...t is connected to the water to air unit forced air heating may be used for the shoulder seasons allowing quick heating to cooling changeover If this feature is used the consumer will easily be able to...

Page 20: ...TEMPERATURE OFFSETS PROGRAM SETTINGS DAYLIGHT SAVINGS SET MONTH DAY YR HR MIN VACATION HOLD DATE THEN TIME SECURITY LOCKOUT TEMP ADJUST LOCKOUT TOTAL KEYPAD LOCKOUT SCREEN SETTINGS PROGRAM SCREEN SERV...

Page 21: ...vised 02 Ja nuary 20 13 INSTALLER MENU BUFFER TANK SETPOINT INPUT DEALER INFORMATION BUFFER TANK DEADBAND OUTDOOR TEMPERATURE RESET RESTORE DEFAULTS MANUAL OPERATION HOT WATER DEADBAND OUTDOOR DESIGN...

Page 22: ...umps Tranqu ility Water to Water THW Ser ies Revis ed 02 J an uary 2013 Electrical Wiring Diagram Matrix Model Diagram Number Voltage Option THW008 010 96B0108N01 220 50 1 THW008 010 96B0108N02 220 50...

Page 23: ...TH E S MAR T SOLU T I ON FOR E N E RG Y E FFI CIENCY 23 climatemaster com Tra nquil it y Wa ter t o Wa ter T HW Series Revised 02 Ja nuary 20 13 Typical Wiring Diagram THW 220 50 1 Units...

Page 24: ...CLIMATEMAS TE R WATE R S OURCE H E A T P UMP S 24 ClimateMaster Water Source Heat Pumps Tranqu ility Water to Water THW Ser ies Revis ed 02 J an uary 2013 Typical Wiring Diagram THW 220 50 1 Units...

Page 25: ...TH E S MAR T SOLU T I ON FOR E N E RG Y E FFI CIENCY 25 climatemaster com Tra nquil it y Wa ter t o Wa ter T HW Series Revised 02 Ja nuary 20 13 Typical Wiring Diagram THW 220 50 1 Units with VSFP...

Page 26: ...MATEMAS TE R WATE R S OURCE H E A T P UMP S 26 ClimateMaster Water Source Heat Pumps Tranqu ility Water to Water THW Ser ies Revis ed 02 J an uary 2013 Typical Wiring Diagram THW 220 50 1 Units with V...

Page 27: ...TH E S MAR T SOLU T I ON FOR E N E RG Y E FFI CIENCY 27 climatemaster com Tra nquil it y Wa ter t o Wa ter T HW Series Revised 02 Ja nuary 20 13 Typical Wiring Diagram THW 220 50 3 Units...

Page 28: ...CLIMATEMAS TE R WATE R S OURCE H E A T P UMP S 28 ClimateMaster Water Source Heat Pumps Tranqu ility Water to Water THW Ser ies Revis ed 02 J an uary 2013 Typical Wiring Diagram THW 220 50 3 Units...

Page 29: ...TH E S MAR T SOLU T I ON FOR E N E RG Y E FFI CIENCY 29 climatemaster com Tra nquil it y Wa ter t o Wa ter T HW Series Revised 02 Ja nuary 20 13 Typical Wiring Diagram THW 220 50 3 Units...

Page 30: ...CLIMATEMAS TE R WATE R S OURCE H E A T P UMP S 30 ClimateMaster Water Source Heat Pumps Tranqu ility Water to Water THW Ser ies Revis ed 02 J an uary 2013 Typical Wiring Diagram THW 220 50 3 Units...

Page 31: ...he control is attempting a retry of a fault the status LED will slow flash slow flash one flash every 2 seconds to indicate the control is in the process of retrying Field Configuration Options Note I...

Page 32: ...he low pressure switch input is bypassed for the initial 120 seconds of a compressor run cycle Low pressure lockout code 3 Water coil low temperature FP1 The FP1 thermistor temperature must be below t...

Page 33: ...mperature range and with flow rates of between 1 6 to 3 2 L M Per kW however usually no more than one of these factors may be at a minimum or maximum level at a time The commissioning table indicates...

Page 34: ...oper range and also verify heating and cooling setpoints for proper operation System pH System water pH is 6 8 5 Proper pH promotes longevity of hoses and fittings System Flushing Water used in the sy...

Page 35: ...r without satisfying the Y input call then the control will go to Lockout mode The last fault causing the lockout will be stored in memory and can be viewed by going into test mode Consult the CXM AOM...

Page 36: ...y These dirty installations are a result of the deterioration of iron or galvanized piping or components in the system or open cooling towers requiring heavy chemical treatment and mineral buildup thr...

Page 37: ...cts damage or insuf cient performance as a result of insuf cient or incorrect system design or the improper application installation or use of CM s products or 14 Electricity or fuel costs or any incr...

Page 38: ...r information contained herein are not express warranties and do not form the basis of any bargain between the parties but are merely ClimateMaster s opinion or commendation of its products ClimateMas...

Reviews: