Tranquility
®
22 (TZ) Series
R e v. : A u g u s t 4 , 2 0 2 1
C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
38
C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S
DXM2 Controls
Conventional
T-stat signal
(Non-Communicating)
Unit
ECM fan
G
Fan only
G, Y1
Stage 1 heating
1
G, Y1, Y2
Stage 2 heating
1
G, Y1, Y2, W
Stage 3 heating
1
G, W
Emergency heat
G, Y1, O
Stage 1 cooling
2
G, Y1, Y2, O
Stage 2 cooling
2
1
Stage 1 = 1st stage compressor, 1st stage fan operation
Stage 2 = 2nd stage compressor, 2nd stage fan operation
Stage 3 = 2nd stage compressor, auxiliary electric heat, 3rd stage fan operation
2
Stage 1 = 1st stage compressor, 1st stage fan operation, reversing valve
Stage 2 = 2nd stage compressor, 2nd stage fan operation, reversing valve
Figure 18: Test Mode Button
Table 6: Unit Operation
DXM2 Control Start-up Operation –
The control will not
operate until all inputs and safety controls are checked for
normal conditions. The compressor will have a 5 minute anti-
short cycle delay at power-up. The first time after power-up
that there is a call for compressor, the compressor will follow
a 5 to 80 second random start delay. After the random start
delay and anti-short cycle delay, the compressor relay will be
energized. On all subsequent compressor calls, the random
start delay is omitted.
P1
Alarm
Relay
Comp
Relay
O
Y1
Y2
W
G
C
R
AL1
24Vdc
EH1
EH2
P6
R
C
Off On
JW3
A
OVR
ESD
C
R
NSB
AL2
JW1
Acc1
Relay
Acc2
Relay
H
COM
NC1
NO1
COM
NC2
NO2
P3
CO
RV
RV
LT1
LT1
LT2
LT2
LP
LP
HP
HP
P7
Status
Fault
R
R
CC
CCG
CO
S1
S2
1
12
1
4
Fa
cto
ry
U
se
(240Vac)
Com
N.O.
Fan Enable
5 1/2"
7"
6 1/2"
5"
Use 4 mounting screws
#6 sheet metal screw 1” long
1.5
3/8” standoff
Factory low
voltage Molex
connection for
unit harness
Factory low
voltage Molex
connection for
electric heat
harness
Micro
U1
Off On
P2
COH
COM
AO2
P11
Gnd T1
P10
T2 T2 T3 T3 T4 T4
T5
P9
T5 T6 T6
A0-1 A0-2
Off On
S3
RV
Relay
CCH
Relay
Test
P5
B-
Gnd
P4
A+ 24V
(240Vac)
Fan Speed
N.O.
N.C.
12V
OUT
Gnd
P8
IN
NC
P12
Note: There is only
one T1 connection
1 2 3 4
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
AO1 Gnd
1
Pust test button to enter Test
Mode and speed-up timing and
delays for 20 minutes.