Tranquility
®
22 (TZ) Series
R e v. : A u g u s t 4 , 2 0 2 1
C l i m a t e M a s t e r Wa t e r-S o u rc e H e a t P u m p s
56
C L I M AT E M A S T E R WAT E R - S O U R C E H E AT P U M P S
Functional Troubleshooting
Note: Never connect refrigerant gauges during startup procedures. Conduct water-side analysis using P/T
ports to determine water flow and temperature difference. If water-side analysis shows poor performance,
refrigerant troubleshooting may be required. Connect refrigerant gauges as a last resort.
Packaged Unit Refrigeration Schematic
Rev. 12/08
Customer: _____________________________________ Antifreeze: ________________________
Model#: ________________________ Serial#: ________________ Loop type: _______________
Complaint: ________________________________________________________________________
COAX
COMPRESSOR
DISCHARGE
SUCTION
HWG
COOLING CYCLE ANALYSIS -
COAX
COMPRESSOR
DISCHARGE
SUCTION
HWG
HEATING CYCLE ANALYSIS -
PSI
SAT
PSI
SAT
°
F
°
F
AIR
COIL
°
F
°
F
FP2: HEATING
LIQUID LINE
°
F
EXPANSION
VALVE
AIR
COIL
°
F
°
F
PSI
SAT
PSI
SAT
°
F
°
F
°
F
°
F
WATER IN
WATER OUT
PSI
PSI
°
F
°
F
WATER IN
WATER OUT
PSI
PSI
Use 500 for water, 485 for antifreeze.
FILTER
DRIER*
FLASH
GAS LINE
°
F
FP1
SENSOR
°
F
EXPANSION
VALVE
FILTER
DRIER*
FP2: FLASH
GAS LINE
°
F
OTHER SIDE
OF FILTR DR
°
F
FP1: CLG
LIQ LINE
°
F
Refrigerant Type:
HFC-410A
Heat of Extraction (Absorption) or Heat of Rejection =
________
flow rate (
diff. (
factor = _____________
(Btu/hr)
Superheat
Subcooling
Suction temperature - suction saturation temp.
Discharge saturation temp. - liquid line temp.
=
=
=
=
(deg F)
(deg F)
gpm) x ________ temp.
deg. F) x ________ fluid
Date: ________________________
Voltage: ________
Comp Amps: _______
Total Amps: ________
Location: ________________________
Model Number: ________________________
Serial Number: ________________________
Look up pressure drop in
I.O.M. or spec. catalog to
determine flow rate.
Look up pressure drop in
I.O.M. or spec. catalog to
determine flow rate.