C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S
Tranquility
®
Compact Belt Drive (TCH/V) Series
Rev.: July 25, 2017
14
C l i m a t e M a s t e r Wa t e r - S o u rc e H e a t P u m p s
TCV300 Dimensional Data
REAR RETURN TOP DISCHARGE (RR/TD)
FRONT RETURN REAR DISCHARGE (FR/RD)
REAR RETURN FRONT DISCHARGE (RR/FD)
FRONT RETURN TOP DISCHARGE (FR/TD)
ALL CONFIGURATIONS REQUIRE SERVICE ACCESS AREA
DESCRIBED IN NOTES 7, 8, and 9
SIDE SERVICE
ACCESS
(See Notes 8)
See Notes
1 and 7
SERVICE ACCESS
·&0
FRONT AND BACK
(See Notes 1 and 7)
(See Note 5)
ALL CONFIGURATIONS
Note 2
(See Note 6)
BLOWER
ROTATION
BLOWER TO AIR COIL
RELATIONSHIP FOR
TOP DISCHARGE
300
BLOWER TO AIR COIL
RELATIONSHIP FOR
REAR OR FRONT
DISCHARGE 300 ONLY
NOTES:
All dimensions in table are inches (cm)
1. While access to all removable panels may not be required, installer should take care
to comply with all building codes and allow adequate clearance for future field service.
2. Water inlet and water outlet connections are factory shipped on the left side. Union
allows field conversion to right side.
3. Condensate drain is available on either side (left or right) of unit. Drain hose and drain
connection will be tied inside the unit. Installer will untie the drain hose, form trap, and
FRQQHFWWRWKHFRQGHQVDWHGUDLQKROHRILQVWDOOHU·VFKRLFH
4. Electrical access is available on either side (left or right) of unit and is also available in
the front on the left or right side of the unit.
5. Overall width - Add 3.12” (8cm) for 1“ (2.5cm) or 2” (5cm) Filter Frame; or 5.12” (13cm)
for 4” (10.2cm) and for front or rear supply add additional 1.06” (2.7cm) for supply
duct collar.
6. Overall cabinet height dimension does not include duct flange for top discharge
configuration.
8QLWVUHTXLUHIHHWFPFOHDUDQFH&$3&63063DQG%63VHUYLFHDFFHVV
6LGHVHUYLFHDFFHVVPXVWEHIHHWFPRQDQ\VLGHWKDWFRQQHFWLRQVDUHPDGH
)LOWHUUHPRYDOLVIURPULJKWRUOHIWVLGHRIILOWHUIUDPHDOORZIHHWFPDFFHVV
for servicing.
Model
Overall Cabinet
Discharge Connection Duct
Flange
Water Connections
Electrical Knockouts
Return Air Connections
Using Return Air Opening
A
Depth
B
Width
C
Height
D
Supply
Width
E
Supply
Depth
F
Supply
Width
G
Supply
Depth
K
Water
Inlet
L
Water
Outlet
M
Conden-
sate
N
O1
O2
P Q R
S
Return
Depth
T
Return
Height
U
V
300
in.
29.0
82.0
69.8
17.5
14.8
6.3
8.6
25.7
3.1
14.5
25.8
8.0
15.0 11.3
1.0
1.5
77.0
35.8
31.7
2.6
cm.
73.7
208.3
177.2
44.5
37.5
16.0
21.8
65.3
7.9
36.8
65.5
20.3 38.1 28.6 2.5
3.8
195.6
90.9
80.5
6.7