About Advanced Features & Operation

The above figure assumes the minimum on time for the prior stage has been met to 
allow the next stage to turn on, once the deadbands have been exceeded.

EMERGENCY HEAT - To initiate the Emergency Heat feature, press the 

FAN

 button. While holding the 

FAN

 button press the 

UP

 button. The Cool 

setpoint display will read ‘EH’ (emergency heat). 

Exit Emergency Heat - Follow the same steps as entering Emergency Heat 

by pressing the FAN and UP buttons. During Emergency Heat, only OFF 

and HEAT modes are available by pressing the MODE button.

Heat

Setpoint

Cool

Setpoint

Deadband

Deadband

Deadband

Deadband

db 1

db 1

db 2

db 2

(adj. 1-6˚ )

(adj. 1-6˚ )

1st Stage

turn on

2nd Stage

turn on

1st Stage

turn on

2nd Stage

turn on

Heating

Cooling

TEMPERATURE

DECREASE

INCREASE

(non-adj. 2˚)

(non-adj. 2˚ )

Deadband

db 3

(non-adj. 2˚)

3rd Stage

strip heat

turn on

FAN

Press for 

Emergency 

Heat

Summary of Contents for ATA32V01

Page 1: ...Geothermal Heatpump Systems with strip heat Up to 3 heat 2 cool ATA32V01 Dual Setpoint Large Easy To Read Display Thermoglow Backlight Auto Changeover No batteries required Locking Keypad Owner s Man...

Page 2: ...e 7 Basic Operation 8 Advanced Setup 9 Advanced Setup Table 12 About Advanced Features Operation 13 Warranty 19 Follow Installation Instructions carefully Disconnect Power to your heatpump before remo...

Page 3: ...Front Panel 2 1 Liquid Crystal Display with Thermoglow 2 Up Down Buttons 3 Mode Button 4 Fan Button 5 Heat or Cool Indicator Red Heat Green Cool 1 4 5 2 3...

Page 4: ...tically changeover between heat and cool modes as the temperature varies OFF Indicates heating and cooling are turned off 2 Clock with Day of the Week Page 6 Indicates the current time and day 3 Room...

Page 5: ...tes the thermostat is in the setup mode 6 Fan On icon Page 8 Indicates constant continuous fan operation When Fan On is not lit indicates the fan will only operate when necessary to heat or to cool 7...

Page 6: ...Wiring Diagrams 5 Single Stage Unit CXM Two Stage Unit DXM R G Y1 W O Y2 C Y W O G R C AL1 AL2 A figure 1 R G Y1 W O Y2 C Y Y2 W1 O W2 G R C AL1 figure 2...

Page 7: ...e Clock and Day Setup Steps 1 2 To set the time and day enter the setup screens by pressing the MODE button and simultaneously pressing the FAN button for 2 seconds During Setup Programming Pressing t...

Page 8: ...h before the furnace will turn on to heat the room Cooling Only The COOL setting indicates the temperature the room has to reach before the air conditioner will turn on to cool the room Heating or Coo...

Page 9: ...nd cool set temperatures simultaneously HEAT OR COOL MODE Pressing the UP or DOWN buttons in Heat OR Cool mode will adjust only the heat OR cool set temperature USING THE FAN BUTTON Fan On indicates c...

Page 10: ...ss to the Advanced Setup Steps that follow the Clock Set steps It is important to note the display will not change and will look the same whether it is in Clock Set or Clock Set plus Advanced Setup MO...

Page 11: ...dvanced Setup Adjust the deadband for the 1st stage 1 6 by pressing the UP and DOWN buttons Adjust the minimum difference between cooling heating setpoints by pressing the UP and DOWN buttons Setup Se...

Page 12: ...two seconds to leave the Setup screens If no buttons are pressed the display will leave the setup screens after 30 seconds On Select backlight operation ON Light continuously OFF Light for 8 seconds a...

Page 13: ...tep Description Pg Range FD 1 SetTime of Day 9 24 hour 12 00am 2 Set Day of Week 9 Monday Sunday Mo 3 Deadband Temp Swing 1st Stage 10 1 6 2 4 Minimum Heat Cool Differential 10 0 6 2 5 Thermoglow Back...

Page 14: ...at in the OFF mode by pressing the MODE button Press and hold the MODE button While holding the MODE button press and hold the DOWN button for 5 seconds All icons will appear on the display Press the...

Page 15: ...nimum of two minutes AND B The temperature spread from the setpoint is equal to or greater than the setpoint plus the 1st stage deadband step 3 page 10 plus the 2nd stage deadband This 2nd stage deadb...

Page 16: ...ill read EH emergency heat Exit Emergency Heat Follow the same steps as entering Emergency Heat by pressing the FAN and UP buttons During Emergency Heat only OFF and HEAT modes are available by pressi...

Page 17: ...ing the MODE button press and hold the DOWN button for 5 seconds All icons will appear on the display After all of the icons appear release the MODE and DOWN buttons Then press and hold the FAN button...

Page 18: ...changeover operation Note To increase the spread between the heating and cooling setpoints press the MODE button until only the heat setpoint is displayed adjust to the desired setpoint Press the MOD...

Page 19: ...OWN buttons together The LOCKED icon will appear on the display then release the buttons To unlock the keypad press and hold the MODE button While holding the MODE button press the UP and DOWN buttons...

Page 20: ...WHATSOEVER ALL WORK UNDER THE TERMS OF THIS WARRANTY SHALL BE PERFORMED DURING NORMAL WORKING HOURS ALL REPLACEMENT PARTS WHETHER NEW OR REMANUFACTURED ASSUME AS THEIR WARRANTY PERIOD ONLY THE REMAIN...

Page 21: ...rev 2 10 19 88 1355...

Reviews: