DEADBAND OPERATION
- Controls up to three Heat and two Cool stages
(please see the diagram on the next page).
The
1st Stage
of heat or cool is turned on when:
(A)
The temperature spread from the setpoint is equal to or greater than:
the setpoint plus the 1st stage deadband (step #3, page 10)
. This 1st
stage deadband is adjustable from 1-6 degrees and the default is two
degrees.
The
2nd Stage
of heat or cool is turned on when:
(A)
The 1st Stage has been on for a minimum of
two minutes
.
AND
(B) The temperature spread from the setpoint is equal to or greater than:
the setpoint plus the 1st stage deadband (step #3, page 10), plus the
2nd stage deadband.
This 2nd stage deadband is fixed at two degrees
and is not adjustable.
The
3rd Stage
of heat is turned on when:
(A)
The 2nd Stage is running for a heat demand.
AND
(B) The temperature spread from the setpoint is equal to or greater than
the setpoint plus the 1st stage deadband (step #3, page 10), plus the
fixed two degree 2nd stage deadband plus the 3rd stage deadband.
The 3rd stage deadband is also fixed at two degrees and is not
adjustable.