1941966
V1.1
3 March 2020
Clevertest and Clevertest Plus
Refer to the supplementary operation guide supplied with the Product.
After Power ON, the Status LED on a Clevertest Plus enabled fitting will display a rapid Green or Red
flashing for a period up to 2 minutes.
Zoneworks and DATA Monitored Options
CLIFE-2PROs with part numbers containing -ZW
, -DATA
are fitted with Zoneworks communications
modules (nodes).These fittings are monitored using either Powerline Carrier Technology that utilises the
power cable to provide data communication or a dedicated data cable to/from data routers installed on a
dedicated data trunk connected to a central Server (can also be connected via Ethernet/Internet/Fibre).
Zoneworks software on the server is used to monitor, coordinate testing and collate test data from each
Lifelight. Zoneworks CLIFE-2PROs can be commissioned by a single push of the test switch, or scanning
of the supplied barcode. The LED Test Switch indicator provides a multifunction indication of the status of
the Lifelight during testing and normal operation:
State
LED Operation
Commissioned
LED on Solid (Green)
Un-commissioned
LED flashes at 0.5Hz (0.5s Green, 0.5s Yellow)
Emergency Light Test In Progress LED flashes at 3s On (Yellow) & 0.5s Off
In the case of the DATA version a 2-way “figure 8” cable and terminal block facilitates the connection to
the DATA network via a multi-drop bus (daisy chain connection). For further information of installation of
a Zoneworks system, please refer to the Zoneworks Users Guide and Commissioning Guide (incl. DATA
version)
DALI EM Option
CLIFE-2PROs with part numbers
containing -DALI
are fitted with DALI modules (nodes) that facilitate
connection and integration to 3
rd
Party Lighting Control Systems. Before installing the –DALI fitting please
confirm that the Lighting Control System has the capability to monitor DALI Emergency Luminaires. The
–DALI fitting will be addressed and configured into the control system by the Lighting Control System
Commissioning Technicians and not Clevertronics.
State
LED Operation
Commissioned/ Un-commissioned LED on Solid (Green)
Emergency Light Test in progress
LED flashes at 1s On (Yellow) & 1s Off
“IDENTIFY COMMAND”
Fitting goes into emergency mode for 10 seconds
A 2-way “figure 8” cable and terminal block facilitates the connection to the DALI network OR a 5/6way
“structured wiring system” lead and plug facilitating the power and DALI connection. DALI connections
are marked as Da Da.
.
LP LIFELIGHT-2PRO-SMS-600
Surface Mount Emergency
Installation & Maintenance Instruction Leaflet
Designed in Australia to comply with the
requirements of AS2293.3: 2005 and AS/NZS
CISPR15: 2011.
NOTE: Standard product codes with this symbol
are enabled with Clevertest Plus capability.
Please refer to the operation guide supplied with
the product for details.
Victoria (Head Office & Manufacturing)
Website:
Email:
Phone:
+61 3 9559 2700
Fax:
+61 3 9559 2799
New South Wales
Phone:
+61 2 8805 6400
Fax:
+61 2 8805 6444
Queensland
Phone:
+61 7 3442 9700
Fax:
+61 7 3442 9777
South Australia/Northern Territory
Phone:
+61 8 8301 8800
Fax:
+61 8 8351 8286
Western Australia
Phone:
+61 8 9248 3720
Fax:
+61 8 9248 3725
New Zealand
Phone:
+64 800 548 448
Models:
CLIFE
-2PRO-SMS-xx-600
Testing
:
Manual Test
xx = Blank
Zoneworks
xx = ZW
Zoneworks DATA xx = DATA
DALI Compatible xx = DALI
Clevertest
xx = CT
(
NOTE: Products supplied with the Clevertest Plus Symbol
are activated with Clevertest PLUS capability. Please refer to the
operation guide supplied with the product for details).
Spare Parts:
1550230
BATT: LP 3.2V 6400mAh.200mm lead.Brkt.
1100869
Lifelight Pro Head Assembly, Ld:280mm,Rnd,LT,Gen 2
CLIFE-PRO-CKIT-NP
LifelightPro,Control Only, LP, NP
Important:
It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation,
ensure that the electricity supply has been switched off and isolated. Installation must be carried out in
accordance with the relevant Australian and International Standards.