Installation:

 

This LIFELIGHT-2PRO-SMS Surface mount non-maintained Emergency Luminaire can be installed on 

solid or T-BAR ceilings or used to replace an existing unit. 

 

Locate the installation position. 

 

Refer Images and Dimensions below for the Cut-out Hole and other dimensions. 

 

Pre-drill mounting holes 

 

Mount base plate and use suitable fixings to secure the base plate into the pilot holes 

 

Bring in supply cables via the rear entry hole or via the end of the base plate (surface mount 

conduit entry) 

 

Terminate the supply cables to the L, N & E terminals (in the case of the –DALI or –DATA fittings 

terminate the DALI or DATA cable to the terminals marked Da Da or DATA). 

 

Install the top cover, containing the LifeLight Pro heads, ensuring to reconnect the Heads assembly 

to the Control Gear.    

 

Ensure the Battery is connected 

 

Screw the cover to the base plate. 

 

If the CTP capabilities are activated, please affix the CTP status label to a visible surface and Four 

Segment Marking on the product will include an ‘’F’’ in third segment block. 

 

Networking: 

When installing the product on a monitored network, (ZONEWORKS, DATA, DALI) simply insert the 

relevant Smart Node PCA. 

 

Images and Dimensions: 

 

 

 

 

 

Testing:

 

 

When the LIFELIGHT 2PRO unit is connected to the un-switched active, it must be allowed to charge 

the battery for at least 24 hours. The emergency lamp only illuminates during a power fail. Conduct the 

following tests: 

 

 

The emergency lamp must illuminate for at least 2 hours after disconnection from the mains. The 

results of all tests are required to be recorded in a service logbook, which is to be kept on-site at all 

times. If the unit fails to illuminate for the requisite time, remedial action must be taken to repair the 

situation and once completed, the unit must pass a subsequent test.  

 

 

Press and hold Test Button or switch Off Mains Supply, check that the emergency lamp is On. 

 

 

Release the Test Button or Switch On Mains Supply, check that the emergency lamp is Off (Non-

maintained operation). 

 

Below are a list of common problems and their possible causes: 

 

Fault:   The Green LED indicator is not illuminated.

 

Check:   A.C. is connected and is turned on. 

 

Battery is connected. 

Test Switch for damage. 

 

Fault:   Lamp does not illuminate in emergency mode. 

 

Check:   A.C. is connected. 

 

Lamp is correctly inserted. 

 

Battery is connected 

 

Fault:   Lamp illuminates in emergency mode, but only stays on for a short period. 

Check:  Battery has been allowed to charge for at least 24 hours. 

 

Battery for damage. 

 

Rated Emergency Lumen Output in accordance with AS2293.1 (refer 

to spacing tables for installation positions):

 

 

 

Refer to the technical label on the product for classification.  

 

Caution:

 

On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during 

construction. As a result, any Lifelight Units, on these circuits, will have their batteries discharged or 

“cycled”. The Li-ion battery in the Lifelight has been selected to give excellent long life performance in a 

controlled IEC 60598-2-22 testing environment. Excessive battery cycling will reduce through-life 

performance and may lead to premature battery failure. Battery warranty claims, as a result of such 

abuse, are specifically EXCLUDED from Clevertronics warranty terms. 

 