1942090 V1.3 3 March 2020
Clevertest and Clevertest Plus
Refer to the supplementary operation guide supplied with the Product.
After Power ON, the Status LED on a Clevertest Plus enabled fitting will display a rapid Green or Red
flashing for a period up to 2 minutes.
Zoneworks and DATA Monitored Options
Lifelights with part numbers
LLIFE-2PRO-ZW-SMS, LLIFE-2PRO-DATA-SMS
are fitted with Zoneworks
communications modules (nodes). These fittings are monitored using either Powerline Carrier Technology
that utilising the power cable to provide data communication or a dedicated data cable to/from data routers
installed on a dedicated data trunk connected to a central Server (can also be connected via
Ethernet/Internet/Fibre). Zoneworks software on the server is used to monitor, coordinate testing and
collate test data from each Lifelight. Zoneworks Lifelights can be commissioned by a single push of the test
switch or scanning of the supplied barcode. The LED Test Switch indicator provides a multifunction
indication of the status of the Lifelight during testing and normal operation:
State
LED Operation
Commissioned
LED on Solid (Green)
Un-commissioned
LED flashes at 0.5Hz (0.5s Green, 0.5s Yellow)
Emergency Light Test In Progress LED flashes at 3s On (Yellow) & 0.5s Off
In the case of the DATA version a 2-way “figure 8” cable and terminal block facilitates the connection to the
DATA network via a multi-drop bus (daisy chain connection). For further information of installation of a
Zoneworks system, please refer to the Zoneworks Users Guide and Commissioning Guide (incl. DATA
version)
DALI EM Option
Lifelights with part numbers L
LIFE-2PRO-DALI-SMS
are fitted with DALI modules (nodes) that facilitate
connection and integration to 3
rd
Party Lighting Control Systems. Before installing the
LLIFE-2PRO-DALI-SMS please confirm that the Lighting Control System has the capability to monitor
DALI Emergency Luminaires. The LLIFE-2PRO-DALI-SMS will be addressed and configured into the
control system by the Lighting Control System Commissioning Technicians and not Clevertronics.
State
LED Operation
Commissioned/ Un-commissioned LED on Solid (Green)
Emergency Light Test in progress
LED flashes at 1s On (Yellow) & 1s Off
“IDENTIFY COMMAND”
Fitting goes into emergency mode for 10 seconds
A 2-way “figure 8” cable and terminal block facilitates the connection to the DALI network OR a 5/6way
“structured wiring system” lead and plug facilitating the power and DALI connection. DALI connections
are marked as Da Da.
LIFELIGHT-2PRO-SMS-600
Surface Mount Emergency Luminaire
Installation & Maintenance Instruction Leaflet
Victoria (Head Office & Manufacturing)
Website:
Email:
Phone:
+61 3 9559 2700
Fax:
+61 3 9559 2799
New South Wales
Phone:
+61 2 8805 6400
Fax:
+61 2 8805 6444
Queensland
Phone:
+61 7 3442 9700
Fax:
+61 7 3442 9777
South Australia/Northern Territory
Phone:
+61 8 8301 8800
Fax:
+61 8 8351 8286
Western Australia
Phone:
+61 8 9248 3720
Fax:
+61 8 9248 3725
New Zealand
Phone:
+64 800 548 448
Designed in Australia to comply with the requirements
of AS2293.3: 2005 and AS/NZS CISPR15: 2011
NOTE: Standard product codes with this symbol are
enabled with Clevertest Plus capability. Please refer to the
operation guide supplied with the product for details.
Models: LLIFE-2PRO-SMS-xx-600-yy
Testing:
Options:
Manual Test
xx = Blank
BLK
yy = BLK
Zoneworks
xx = ZW
Z/W DATA
xx = DATA
DALI Comp.
xx = DALI
Clevertest
xx = CT
(NOTE: -CT Products supplied with the Clevertest Plus Symbol are activated with
Clevertest PLUS capability. Please refer to the operation guide supplied with the product for
Spare Parts:
1530230
Battery, L10 3.3V 5Ahr, 200mm Lead Bracket
1100869
Lifelight Pro Head Assembly, Ld:280mm,Rnd,LT,Gen 2
LLIFE-PRO-CKIT-NP
Lifelight Pro,Control Only,Batten,L10, NP
Important:
It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before
installation, ensure that the electricity supply has been switched off and isolated. Installation must be
carried out in accordance with the relevant Australian and International Standards.