1942090        V1.3        3 March 2020 

 

   

 

 

Initial Testing:

 

 

When the LIFELIGHT 2PRO unit is connected to the un-switched active, it must be allowed to charge the 

battery for at least 24 hours. The emergency lamp only illuminates during a power failure. Conduct the 

following tests: 

 

 

During the first commissioning test the emergency lamp must illuminate for at least 2 hours after 

disconnection from the main supply. The results of all tests are required to be recorded in a service 

logbook, which is to be kept on-site at all times. If the unit fails to illuminate for the requisite time, 

remedial action must be taken to repair the situation and once completed, the unit must pass a 

subsequent test.   

 

 

Press and hold Test Button for each LED head or switch Off Mains Supply, check that the emergency 

lamps are On. 

 

 

Release the Test Button or Switch on Mains Supply, check that the emergency lamp is Off 

(Non-maintained operation). 

 

Below are a list of common problems and their possible causes: 

 

Fault:    The Green LED indicator is not illuminated.

 

Check:    A.C. is connected and is turned on. 

 

Battery is connected. 

Test Switch for damage. 

 

Fault:    Lamp does not illuminate in emergency mode. 

 

Check:    A.C. is connected. 

 

Lamp is correctly inserted. 

 

Battery is connected 

 

Fault:    Lamp illuminates in emergency mode, but only stays on for a short period. 

Check:  Battery has been allowed to charge for at least 24 hours. 

 

Battery for damage. 

 

Rated Emergency Lumen Output in accordance with AS2293.1 (refer to 

spacing tables for installation positions):

 

 

 

Refer to the Technical Label for classification information. 

 

Caution:

 

On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during 

construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries discharged 

or “cycled”. The battery in this fitting has been selected to give excellent long-life performance in a 

controlled AS2293 testing environment. Excessive battery cycling will reduce through-life performance and 

may lead to premature battery failure. Battery warranty claims, as a result of such abuse, are specifically 

EXCLUDED from Clevertronics warranty terms. 

 

Warranty:

 

For Product Warranty information and Terms and Conditions of Sales please refer to our website 

http://clevertronics.com.au/terms-conditions-sale-australia-nz/

 

 

Installation:

 

 

This LIFELIGHT-2PRO-SMS Surface mount non-maintained Emergency Luminaire can be installed on 

solid or T-BAR ceilings or used to replace an existing unit. 

 

Locate the installation position. 

 

Refer Images and Dimensions below for the Cut-out Hole and other dimensions. 

 

Pre-drill mounting holes 

 

Mount base plate and use suitable fixings to secure the base plate into the pilot holes 

 

Bring in supply cables via the rear entry hole or via the end of the base plate (surface mount 

conduit entry) 

 

Terminate the supply cables to the L, N & E terminals (in the case of the –DALI or –DATA fittings 

terminate the DALI or DATA cable to the terminals marked Da Da or DATA). 

 

Install the top cover, containing the control gear, ensuring to reconnect the control gear assembly 

to the connector from the supply terminal block   

 

Ensure the Battery is connected 

 

Screw the cover to the base plate and, in the case of side/conduit entry remove the knock-out at 

the end of the cover. 

 

If the CTP capabilities are activated, please affix the CTP status label to a visible surface and Four 

Segment Marking on the product will include an ‘’F’’ in third segment block. 

 

Networking: 

When installing the product on a monitored network, (ZONEWORKS, DATA, DALI) simply insert the 

relevant Smart Node PCA. 

 

 

 

 