Installation:

 

This LLIFE-PRO-SMS-SPOT Surface Mount Non-Maintained Emergency Luminaire can be installed on 
solid or T-BAR ceilings or used to replace an existing unit. 

 

Locate the installation position. 

 

Remove the top cover (containing the control gear) from the base plate via the two fixing screws on 
the top cover.  Disconnect the mains supply cable via the connector between the base and top 
cover. 

 

Refer Images and Dimensions below for the Cut-out Hole and other dimensions. 

 

Pre-drill mounting holes. 

 

Mount base plate and use suitable fixings to secure the base plate into the pilot holes. 

 

Bring in supply cables via the rear entry hole or via the end of the base plate (surface mount 
conduit entry). 

 

Terminate the supply cables to the L, N & E terminals (in the case of the 

–DALI or –DATA fittings 

terminate the DALI or DATA cable to the terminals marked Da Da or DATA). 

 

Install the top cover, containing the control gear, ensuring to reconnect the control gear assembly 
to the connector from the supply terminal block. 

 

Ensure the Battery is connected. 

 

Screw the cover to the base plate, and in the case of side/conduit entry remove the knock-out at 
the end of the cover to go cover the conduit. 
 

Networking: 

When installing the product on a monitored network, (ZONEWORKS, DATA, DALI) simply insert the 
relevant Smart Node PCA. 

 

Dimensions:

        

    
 
 
 
 
 
                        

 

Testing:

 

Once connected to the 240V mains supply, the unit must be allowed to charge the battery for at least 24 
hours. Conduct the following tests: 

 

For the first test, the emergency lamp must remain illuminated for at least 2 hours after 
disconnection from the mains supply. 

 

Subsequent tests require the unit to illuminate for at least 90 minutes. The results of all tests are 
required to be recorded in a service logbook, which is to be kept on-site at all times. If the unit fails 
to remain illuminated for the requisite time, remedial action must be taken to repair the situation 
and once completed, the unit must pass a subsequent test. For more specific information, please 
refer to the current edition of the AS 2293.3 Standard. 

 

Trouble Shooting: 

Below are a list of common problems and their possible causes. 

 
Fault:  

The Green LED Test Switch indicator is not illuminated.

 

Check:   A.C. is connected and is turned on. 
 

Battery is connected 
Test Switch for damage. 
 

Fault:  

Lamp does not illuminate in emergency mode. 

 

Check:   A.C. is connected. 
 

Lamp is correctly inserted. 

 

Battery is connected 

 

Fault:  

Lamp illuminates in emergency mode, but only stays on for a short period. 

Check: 

Battery has been allowed to charge for at least 24 hours. 

 

Battery for damage. 

 

 

Caution:

 

On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during 
construction. As a result, any Exit & Emergency Units, on these circuits, will have their batteries 
discharged or “cycled”. The battery in this fitting has been selected to give excellent long-life 
performance in a controlled AS2293 testing environment. Excessive battery cycling will reduce through-
life performance and may lead to premature battery failure. Battery warranty claims, as a result of such 
abuse, are specifically EXCLUDED from Clevertronics warranty terms. 